Phoenix Contact Bus coupler IBS IL 24 BK RB-LK-PAC 2861506 2861506 データシート

製品コード
2861506
ページ / 5
Nov 13, 2013    2 / 5
Technical data
General
Test section
7.5 V logics supply, 24 V analog supply, 24 V bus terminal module
supply/functional earth ground 500 V AC 50 Hz 1 min
Interfaces
Fieldbus system
Lokalbus
Name
Inline local bus
Connection method
Inline data jumper
Transmission speed
500 kBit/s
Transmission physics
FO
Fieldbus system
INTERBUS
Name
INTERBUS remote bus
Connection method
6x F-SMA connector
Transmission speed
500 kBit/s
Transmission physics
FO
Name
Supply
Connection method
8-pos. Inline connector
System limits of the bus coupler
Number of local bus devices that can be connected
63
Number of devices with parameter channel
62
Number of branch terminals with remote bus branch
max. 15
Power supply for module electronics
Connection method
Inline plugs
Supply voltage
24 V DC (via Inline plug)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current consumption
max. 1.3 A (with max. number of connected I/O terminal blocks)
Inline potentials
Communications power U
L
7.5 V DC ±5 %
Power supply at U
L
max. 2 A DC (observe derating)
I/O supply voltage U
ANA
24 V DC -15% / +20%
Power supply at U
ANA
max. 0.5 A DC (observe derating)
classifications
eCl@ss
eCl@ss 4.0
27250203
eCl@ss 4.1
27250203
eCl@ss 5.0
27250203
eCl@ss 5.1
27242608
eCl@ss 6.0
27242608
eCl@ss 7.0
27242608
eCl@ss 8.0
27242608