Wago 750-340 PROFINET IO FELDBUS-COUPLER 100 MBIT 750-340 データシート

製品コード
750-340
ページ / 2
750-340
Subject to design changes
WAGO Kontakttechnik GmbH & Co. KG
Postfach 2880 • D-32385 Minden Tel.:  +49(0)571 /887-0
E-Mail: info@wago.com
31.07.2006
Hansastr. 27
• D-32423 Minden Fax.: +49(0)571 /887-169 www.wago.com
PROFINET IO Fieldbus Coupler
10/100 Mbits/s; digital and analog signals
Data contacts 
Fieldbus 
connection 
RJ 45 
 
Power jumper contacts 
0 V 
Supply via 
power jumper contacts 
24 V 
 
Supply 
24 V 
0 V 
 
Status  
voltage supply 
-System 
-Power jumper contacts 
Configuration 
interface 
24V  0V 
+  + 
—  — 
01 02 
LINK 
MS 
NS 
I/O 
PROFINET IO 

TxD/RxD 
750- 340
 
This fieldbus coupler allows the connection of the WAGO I/O SYSTEM as a sla-
ve device on a PROFINET IO industrial ethernet network.  
The fieldbus coupler supports all WAGO I/O SYSTEM modules. 
The coupler automatically configures itself, creating a local process image which 
may include analog, digital, or specialty module data.  Analog and specialty 
module data is sent via words and/or bytes.  
Digital data is packed into words or bytes.
The fieldbus coupler is integrated into the application as a PROFINET IO device.  
The coupler also supports many common ethernet protocols for system ma-
nagement and diagnostics (HTTP, BootP, DHCP, DNS, SNTP, FTP, and SNMP).
Description
Item no.
Pack. 
unit
PROFINET IO 100 MBit
750-340
1
Accessories
Item no.
Pack. 
unit
Miniature WSB Quick marking system
plain
248-501
5
with marking
see pages 224 ... 225
Approvals
Conformity marking
1
System data
No. of couplers connected to Master
limited by ETHERNET specification
Transmission medium
Twisted Pair S-UTP 100 Ω cat. 5
Max. length of fieldbus segment
100 m between hub station and 750-340 
max. legth of network limited by 
ETHERNET specification
Baud rate
10/100 Mbits/s
Buscoupler connection
RJ45
Protocols
PROFINET RT V 2.0, HTTP, DHCP, DNS, 
SNTP, FTP, SNMP