Wago 750-333 PROFIBUS DP/V1 FIELD BUSCOUPLER 12 MBaud 750-333 データシート

製品コード
750-333
ページ / 2
750-333
Subject to design changes
WAGO Kontakttechnik GmbH & Co. KG
Postfach 2880 • D-32385 Minden Tel.:  +49(0)571 /887-0
E-Mail: info@wago.com
31.07.2006
Hansastr. 27
• D-32423 Minden Fax.: +49(0)571 /887-169 www.wago.com
PROFIBUS DP/V1 Fieldbus Coupler
12 Mbaud; digital and analog signals
Data Contacts 
Fieldbus 
connection 
D-Sub 
Address 
 
Power jumper contacts 
0 V 
Supply via 
power jumper contacts 
24 V 
 
Supply 
24 V 
0 V 
 
Status 
voltage supply
-System
-Power jumper contacts
Address 
 
Configuration 
interface 
24V  0V 
+  + 
—  — 
01  02 
RUN 
BF 
DIA 
I/O 
PROFIBUS 
x1 
0 1 2 3 
4  5 6 7 
8 9 
x1 
0 1 2 3 
4  5 6 7 
8 9 
ADDRESS 

BUS 
750- 333
 
This buscoupler interfaces the I/O modules of the WAGO-I/O-SYSTEM to 
PROFIBUS DP.
When initializing, the buscoupler determines the module structure of the node, 
to create the process image in Profibus. In order to optimize addresses, the I/O 
modules with a bit width smaller than 8 are grouped in one byte.
It is furthermore possible to deactive I/O modules and to modify the image of 
the node according to the connected signals without having to modify the exis-
ting application.
The diagnosis concept is based on diagnostics according to the EN 50170 Stan-
dard. Therefore the programming of modules is not necessary to interpret the 
diagnostic information from each manufacturer.
Note: GSD files required
Description
Item no.
Pack. 
unit
PROFIBUS DP/V1 12MBd
750-333
1
Accessories
Item no.
Pack. 
unit
GSD files
Download: www.wago.com
Miniature WSB Quick marking system
plain
248-501
5
with marking
see pages 224 ... 225
Standards and Approvals
Standard
EN 50170
r
 UL 508
Marine applications
see pages 36 ... 39
4
 EN 50021
II 3 GD EEx nA II T4
4
 r  UL 1604
Class I Div2 ABCD T4A
Conformity marking
1
System data
No. of couplers connected to Master
96 with repeater
Max. no. Of I/O points
ca. 6000 (depends on master)
Transmission medium
Cu-cable acc. to EN 50170
Max. length of fieldbus segment
100 m ... 1200 m  (depends on the baud 
rate / on the cable)
Baud rate
9.6 kbaud ... 12 Mbaud
Transmission time
typ. 1 ms (10 Modules; 32 I, 32 O/Mod; 
at 12 Mbaud and digital Signals) 
max. 3.3 ms
Buscoupler connection
1 x D-Sub 9; socket