Tele 1340200 E1IM10AACL10 Gamma 1-Phase Current Monitoring Relay 1-phase current monitoring in 230 V/AC network 1340200 データシート
製品コード
1340200
Subject to alterations and errors
Release 10/06
Monitoring relays - ENYA series
AC current monitoring in 1-phase mains
Multifunction
1 change over contact
Width 17.5 mm
Installation design
Technical data
1. Functions
AC current monitoring in 1-phase mains with adjustable threshold,
hysteresis and tripping delay.
hysteresis and tripping delay.
OVER
Overcurrent
monitoring
UNDER
Undercurrent
monitoring
WIN
Monitoring the window between
Min
and
Max
OVER+Latch
Overcurrent monitoring with fault latch
UNDER+Latch
Undercurrent monitoring with fault latch
WIN+Latch
Monitoring the window between
Min and Max with fault latch
2. Time ranges
Adjustment
range
Start-up suppression time (Start):
-
Tripping delay (Delay):
0,1 to 10s
3. Indicators
Green LED ON/OFF:
indication of supply voltage
Red LED ON/OFF:
indication of failure of the
corresponding
threshold
Red LED flashes:
indication of tripping delay of
the corresponding threshold
Yellow LED ON/OFF:
indication of output relay
4. Mechanical design
Self extinguishing plastic housing, IP rating IP40
Mounted on DIN rail TS 35 according to EN 50022
Mounting position:
Mounted on DIN rail TS 35 according to EN 50022
Mounting position:
any
Shockproof terminal connection according to VBG 4 (PZ1 required),
IP rating IP20
Tightening torque:
IP rating IP20
Tightening torque:
max. 1Nm
Terminal capacity:
1 x 0.5 to 2.5mm² with/without multicore cable end
1 x 4mm² without multicore cable end
2 x 0.5 to 1.5mm² with/without multicore cable end
2 x 2.5mm² flexible without multicore cable end
5. Input circuit
Supply voltage:
230V AC
Terminals: Li-N
Tolerance:
Tolerance:
-15% to +15% of Un
Rated consumption:
5VA (0.8W)
Rated frequency:
AC 48 to 63Hz
Duration of operation:
100%
Reset time:
500ms
Wave form:
Sinus
Hold-up time:
-
Drop-out voltage:
>20% of rated voltage
Overvoltage category:
III (according to IEC 60664-1)
Rated surge voltage:
4kV
6. Output circuit
1 potential free change over contact
Rated voltage:
Rated voltage:
250V AC
Switching capacity:
1250VA (5A / 250V)
Fusing:
5A fast acting
Mechanical life:
20 x 10
6
operations
Electrical life:
2 x 10
5
operations
at 1000VA resistive load
Switching frequency:
max. 60/min at 100VA resistive load
max. 6/min at 1000VA resistive load
(according to IEC 947-5-1)
Overvoltage category:
III. (according to IEC 60664-1)
Rated surge voltage:
4kV
7. Measuring circuit
Measuring variable:
AC sinus, 48 to 63Hz
Measuring input:
10A AC
Terminals: Li,
Lk
Overload capacity:
13A (ex 10A - distance > 5mm)
Starting current:
1s
1s
100A
3s
50A
Input resistance:
3m
Ω
Switching threshold Us:
see table ordering information or
printing on the unit
Hysteresis H:
see table ordering information or
printing on the unit
Overvoltage category:
III (according to IEC 60664-1)
Rated surge voltage:
4kV
8. Accuracy
Base accuracy:
±5% of nominal value
Adjustment accuracy:
±5% of nominal value
Repetition accuracy:
≤2% of nominal value
Voltage influence:
-
Temperature influence:
0,05% / °C
9. Ambient conditions
Ambient temperature:
-25 to +55°C (according to IEC 68-1)
Storage temperature:
-25 to +70°C
Transport temperature:
-25 to +70°C
Relative humidity:
15% to 85%
(according to IEC 721-3-3 class 3K3)
Pollution degree:
2, if built in 3
(according to IEC 664-1)
Vibration resistance:
10 to 55 Hz 0.35mm
(according to IEC 68-2-6)
Shock resistance:
15g 11ms
(according to IEC 68-2-27)
10. Weight
Single packing:
72g
Package of 10pcs:
655g per package
E1IM