Tele 111100 Time Delay Relay, Timer, DPDT-CO 12 - 240 V DC/AC 111100 ユーザーズマニュアル
製品コード
111100
E3ZM20
www.tele-online.com
Timers - Multifunction
ENYA series
7 Functions
7 time ranges
Wide input range
2 change over contacts
Width 35mm
Installation design
7 Functions
7 time ranges
Wide input range
2 change over contacts
Width 35mm
Installation design
Technical data
1. Functions
The function has to be set before connecting the relay to the supply
voltage.
E
ON delay
R
OFF delay
Ws
Single shot leading edge with control input
Wa
Single shot trailing edge with control input
Es
ON delay with control input
Wu
Single shot leading edge voltage controlled
Bp
Flasher pause first
2. Time ranges
Time range Adjustment range
1s
50ms
1s
10s
500ms
10s
1min
3s
1min
10min 30s
10min
1h
3min
1h
10h
30min
10h
100h 5h
100h
3. Indicators
Green LED U/t ON:
indication of supply voltage
Green LED U/t flashes: indication of time period
Yellow LED R ON/OFF: indication of relay output
4. Mechanical design
Self-extinguishing plastic housing, IP rating IP40
Mounted on DIN-rail TS 35 according to EN 60715
Mounting position: any
Shockproof terminal connection according to VBG 4 (PZ1 required),
IP rating IP20
Tightening torque: max. 1Nm
Terminal capacity:
1 x 0.5 to 2.5mm² with/without multicore cable end
1 x 4mm² without multicore cable end
2 x 0.5 to 1.5mm² with/without multicore cable end
2 x 2.5mm² flexible without multicore cable end
5. Input circuit
Supply voltage:
12 to 240V AC/DC
Terminals:
A1(+)-A2
Tolerance:
-10% to +10%
Rated consumption:
6VA (2W)
Rated frequency:
AC 48 to 63Hz
Duty cycle:
100%
Reset time:
100ms
Residual ripple for DC: 10%
Drop-out voltage:
>30% of minimum rated supply voltage
Overvoltage category: III (in accordance with IEC 60664-1)
Rated surge voltage:
4kV
6. Output circuit
2 potential free change over contacts
Rated voltage:
250V AC
Switching capacity:
2000VA (8A / 250V)
Fusing:
8A fast acting
Mechanical life:
20 x 10
6
operations
Electrical life:
2 x 10
5
operations
at 1000VA resistive load
Switching frequency:
max. 6/min at 1000VA resistive load
(in accordance with IEC 60947-5-1)
Overvoltage category: III (in accordance with IEC 60664-1)
Rated surge voltage:
4kV
7. Control input
Input not potential free: terminals A1-B1
Loadable:
yes
Max. line length:
10m
Trigger level (sensitivity): automatic adaption to supply voltage
Min. control pulse length: DC 50ms / AC 100ms
8. Accuracy
Base accuracy:
±1% of maximum scale value
Adjusting accuracy:
<5% of maximum scale value
Repetition accuracy:
<0.5% or ±5ms
Voltage influence:
-
Temperature influence: ≤0.01% / °C
9. Ambient conditions
Ambient temperature:
-25 to +55°C
Storage temperature:
-25 to +70°C
Transport temperature: -25 to +70°C
Relative humidity:
15% to 85%
(in accordance with IEC 60721-3-3 class 3K3)
Pollution degree:
2, if built in 3
(in accordance with IEC 60664-1)
10. Weight
Single packing:
106g