Siemens 6GK7242-7KX30-0XE0 ユーザーズマニュアル
![Siemens](https://files.manualsbrain.com/attachments/fea10bc852adcb1f4f76708d5daebca542e532b9/common/fit/150/50/c53f5738b57089fc3d6c279e23db7450685a19c9616727fc1f659077967b/brand_logo.png)
Configuration and programming
5.4 Programming the telecontrol instructions
CP 1242-7
Operating Instructions, 03/2012, C79000-G8976-C247-03
Operating Instructions, 03/2012, C79000-G8976-C247-03
61
DONE ERROR STATUS
Meaning
0
1
80F5
H
Invalid connection endpoint:
Connection establishment by TC_CON failed.
Connection establishment by TC_CON failed.
or
Connection terminated by remote partner: First call TC_DISCON.
0
1
80F6
H
Format error of a parameter in the called data block (wrong length, wrong format or
invalid value)
Check the configuration of the "TC_CON..." SDT.
Check the configuration of the "TC_CON..." SDT.
5.4.4
TC_RECV: Receive data via the GSM network
Meaning
The TC_RECV instruction allows the reception of data via programmed connections of the
following types:
● ISO-ON-TCP connections
● SMS connections
● ISO-ON-TCP connections
● SMS connections
To receive SMS messages, the phone number of the sender must be configured in the
STEP 7 configuration of the receiving CP (authorized phone numbers). The sender must
support the CLIP function.
The phone number of the connection partner must be entered in the "TCON_PHONE"
The phone number of the connection partner must be entered in the "TCON_PHONE"
SDT.
Wake-up SMS messages are filtered out.
Wake-up SMS messages are filtered out.
● Telecontrol connections
Note
Receiving SMS messages from different senders
If you want to receive SMS messages from different senders, you have two alternatives:
You configure several connections (TC_CON, TC_RECV, TC_DISCON).
Receiving SMS messages from different senders
If you want to receive SMS messages from different senders, you have two alternatives:
You configure several connections (TC_CON, TC_RECV, TC_DISCON).
or
You may only enter no telephone number for only one configured connection in the
required data block "TCON_PHONE" in the "PhoneNumber" parameter. When receiving
messages, this is then interpreted as a placeholder for all authorized connection partners.
You will find more detailed information on the connection types in the description of the
TC_CON instruction.
The ID parameter references the GPRS connection. The value of ID must correspond to the
The ID parameter references the GPRS connection. The value of ID must correspond to the
value used for ID by TC_CON.
The INTERFACE parameter references the GPRS interface of the required local CP. The
The INTERFACE parameter references the GPRS interface of the required local CP. The
value must be the same as that used by TC_CON for INTERFACE.