Siemens 6GK7242-7KX30-0XE0 ユーザーズマニュアル

ページ / 108
 
Configuration and programming 
 
5.4 Programming the telecontrol instructions 
CP 1242-7 
Operating Instructions, 03/2012, C79000-G8976-C247-03 
61
 
DONE  ERROR  STATUS 
Meaning 
80F5
H
 
Invalid connection endpoint: 
  Connection establishment by TC_CON failed. 
or 
  Connection terminated by remote partner: First call TC_DISCON. 
80F6
H
 
Format error of a parameter in the called data block (wrong length, wrong format or 
invalid value) 
Check the configuration of the "TC_CON..." SDT. 
5.4.4 
TC_RECV: Receive data via the GSM network 
Meaning 
The TC_RECV instruction allows the reception of data via programmed connections of the 
following types: 
●  ISO-ON-TCP connections 
●  SMS connections 
To receive SMS messages, the phone number of the sender must be configured in the 
STEP 7 configuration of the receiving CP (authorized phone numbers). The sender must 
support the CLIP function. 
The phone number of the connection partner must be entered in the "TCON_PHONE" 
SDT. 
Wake-up SMS messages are filtered out. 
●  Telecontrol connections 
 
 
Note 
Receiving SMS messages from different senders   
If you want to receive SMS messages from different senders, you have two alternatives: 
  You configure several connections (TC_CON, TC_RECV, TC_DISCON). 
or 
  You may only enter no telephone number for only one configured connection in the 
required data block "TCON_PHONE" in the "PhoneNumber" parameter. When receiving 
messages, this is then interpreted as a placeholder for all authorized connection partners.
 
You will find more detailed information on the connection types in the description of the 
TC_CON instruction. 
The ID parameter references the GPRS connection. The value of ID must correspond to the 
value used for ID by TC_CON. 
The INTERFACE parameter references the GPRS interface of the required local CP. The 
value must be the same as that used by TC_CON for INTERFACE.