6.3 Powerful instructions make programming easy 
Easy Book 
Manual, 03/2014, A5E02486774-AF 
109
 
 
As long as the timer runs, the state of DB1.MyIEC_Timer.Q=1 and the Tag_Output value=1. 
When the Tag_Time value has elapsed, then DB1.MyIEC_Timer.Q=0 and the Tag_Output 
value=0. 
6.3.6 
Counters 
You use the counter instructions to count internal program events and external process 
events.  
●  The "count up" counter (CTU) counts up by 1 when the value of the input parameter CU 
changes from 0 to 1. 
●  The "count down" counter (CTD) counts down by 1 when the value of input parameter CD 
changes from 0 to 1. 
●  The "count up and down" counter (CTUD) counts up or down by 1 on the 0 to 1 transition 
of the count up (CU) or count down (CD) inputs. 
S7-1200 also provides high-speed counters (Page 118) (HSC) for counting events that occur 
faster than the OB execution rate.  
The CU, CD, and CTUD instructions use software counters whose maximum counting rate is 
limited by the execution rate of the OB they are placed in. 
 
 
Note 
If the events to be counted occur within the execution rate of the OB, use CTU, CTD, or 
CTUD counter instructions. If the events occur faster than the OB execution rate, then use 
the HSC. 
 
Each counter uses a structure stored in a data block to maintain counter data. For SCL, you 
must first create the DB for the individual counter instruction before you can reference it. For 
LAD and FBD, STEP 7 automatically creates the DB when you insert the instruction. 
The number of counters that you can use in your user program is limited only by the amount 
of memory in the CPU. Individual counters use 3 bytes (for SInt or USInt), 6 bytes (for Int or 