Easy to communicate between devices 
 
7.6 PROFIBUS 
 
Easy Book 
144
 
Manual, 03/2014, A5E02486774-AF 
7.6.1 
Communications services of the PROFIBUS CMs 
The PROFIBUS CMs use the PROFIBUS DP-V1 protocol. 
Types of communication with DP-V1 
The following types of communication are available with DP-V1: 
●  Cyclic communication (CM 1242-5 and CM 1243-5) 
Both PROFIBUS modules support cyclic communication for the transfer of process data 
between DP slave and DP master. 
Cyclic communication is handled by the operating system of the CPU. No software blocks 
are required for this. The I/O data is read or written directly from/to the process image of 
the CPU. 
●  Acyclic communication (CM 1243-5 only) 
The DP master module also supports acyclic communication using software blocks: 
–  The "RALRM" instruction is available for interrupt handling. 
–  The "RDREC" and "WRREC" instructions are available for transferring configuration 
and diagnostics data. 
Functions not supported by the CM 1243-5: SYNC/FREEZE and Get_Master_Diag 
Other communications services of the CM 1243-5 
The CM 1243-5 DP master module supports the following additional communications 
services: 
●  S7 communication 
–  PUT/GET services 
The DP master functions as a client and server for queries from other S7 controllers or 
PCs via PROFIBUS. 
–  PG/OP communication 
The PG functions allow the downloading of configuration data and user programs from 
a PG and the transfer of diagnostics data to a PG. 
Possible communications partners for OP communication are HMI panels, SIMATIC 
panel PCs with WinCC flexible or SCADA systems that support S7 communication.