PLC concepts made easy 
 
4.4 Memory areas, addressing and data types 
 
Easy Book 
62
 
Manual, 03/2014, A5E02486774-AF 
4.4.2 
Addressing memory areas 
STEP 7 facilitates symbolic programming. You create symbolic names or "tags" for the 
addresses of the data, whether as PLC tags relating to memory addresses and I/O points or 
as local variables used within a code block. To use these tags in your user program, simply 
enter the tag name for the instruction parameter. For a better understanding of how the CPU 
structures and addresses the memory areas, the following paragraphs explain the "absolute" 
addressing that is referenced by the PLC tags. The CPU provides several options for storing 
data during the execution of the user program: 
●  Global memory: The CPU provides a variety of specialized memory areas, including 
inputs (I), outputs (Q) and bit memory (M). This memory is accessible by all code blocks 
without restriction.  
●  Data block (DB): You can include DBs in your user program to store data for the code 
blocks. The data stored persists when the execution of the associated code block comes 
to an end. A "global" DB stores data that can be used by all code blocks, while an 
instance DB stores data for a specific FB and is structured by the parameters for the FB.  
●  Temp memory: Whenever a code block is called, the operating system of the CPU 
allocates the temporary, or local, memory (L) to be used during the execution of the 
block. When the execution of the code block finishes, the CPU reallocates the local 
memory for the execution of other code blocks.  
Each different memory location has a unique address. Your user program uses these 
addresses to access the information in the memory location.  
References to the input (I) or output (Q) memory areas, such as I0.3 or Q1.7, access the 
process image. To immediately access the physical input or output, append the reference 
with ":P" (such as I0.3:P, Q1.7:P, or "Stop:P").  
Forcing applies a fixed value to a physical input (Ix.y:P) or a physical output (Qx.y:P) only. 
To force an input or output, append a ":P" to the PLC tag or the address. For more 
Table 4- 4 
Memory areas 
Memory area 
Description 
Force 
Retentive 
I  
Process image input 
I_:P
1
 
(Physical input) 
Copied from physical inputs at the beginning of the scan 
cycle 
No 
No 
Immediate read of the physical input points on the CPU, 
SB, and SM 
Yes 
No 
Q  
Process image output 
Q_:P
1
 
(Physical output) 
Copied to physical outputs at the beginning of the scan 
cycle 
No 
No 
Immediate write to the physical output points on the 
CPU, SB, and SM 
Yes 
No 
M  
Bit memory 
Control and data memory 
No 
Yes 
(optional) 
Temp memory 
Temporary data for a block local to that block 
No 
No 
DB 
Data block 
Data memory and also parameter memory for FBs 
No 
Yes  
(optional) 
 
1
  To immediately access (or to force) the physical inputs and physical outputs, append a ":P" to the address or tag (such 
as I0.3:P, Q1.7:P, or "Stop:P").