EZ800/EZD Control Commands
MN05013001E
96
Table 43: Byte 4 – 8: Data 1 – 5
Winter/summer time, DST
Telegram structure
Byte
Contents
Value (hex)
4
Data 1
Hour (0 to 23)
00 – 17
5
Data 2
Minute (0 to 59)
00 – 3B
6
Data 3
Day (1 to 28; 29, 30, 31; 
depending on month and 
year)
01 – 1F
7
Data 4
Month (1 to 12)
01 – 0C
8
Data 5
Year (0 – 99,
corresponds to 2000 – 2099)
00 – 63
Byte
Meaning
Value (hex), sent by
Master
Slave
0
Toggle byte
J
page 94
1
Command
Read
93
Write
B3
Response
Read 
successful
C2
Write 
successful
C1
Command 
rejected
C0
2
Len
05
05
3
Index
01
01
4 – 8
Data 1 – 5
Read operation
00
J
Table 44
For write 
operation
J
Table 44
00