Eaton Electrical PROFIBUS-DP EZ204-DP ユーザーズマニュアル
Read/write image data
For more information visit: www.EatonElectrical.com
MN05013001E
103
Read local analog inputs IA1 to IA4
The analog inputs on the EZ800 and EZD basic units can be
The analog inputs on the EZ800 and EZD basic units can be
read directly via PROFIBUS-DP. The 16-bit value is
transferred in Intel format (LowByte first).
Telegram structure
Telegram structure
Byte
Meaning
Value (hex), sent by
Master
Slave
0
Toggle byte
J
page 94
1
Command: Read
91
–
Response:
Read successful
–
C2
Command
rejected
–
C0
2
Len
02
02
3
Type
02
02
4
Index
01 – 04
1
01 – 04
1
5
Data 1 (Low Byte)
00
See example
6
Data 2 (High Byte)
00
See example
7 – 8
Data 3 – 4
00
00
1) 01 = Analog input I7
02 = Analog input I8
03 = Analog input I11
04 = Analog input I12