Read/write image data
For more information visit: www.EatonElectrical.com
MN05013001E
107
Read and write local QW0 outputs/outputs of the stations 
QW1 to QW8
You can read and write the local outputs directly via 
PROFIBUS-DP. However, the outputs are only switched 
externally if the device is in Run mode and the addressed 
output is not being used in the circuit diagram. 
Byte
Meaning
Value (hex), sent by
Master
Slave
0
Toggle byte
J
page 94
1
Command
Read
91
Write
B1
Response
Read 
successful
C2
Write successful
C1
Command 
rejected
C0
2
Len
02
02
3
Type
04
04
4
Index
1
00/01 – 08
00/01 – 08
5
Data  1
Read operation
00
J
Table 46
For write 
operation
J
Table 47
00
6 – 8
Data 2 – 4
00
00
1) 00 = Local output
01 – 08 = Outputs of network stations 1 – 8