EZ800/EZD Control Commands
MN05013001E
110
Reading local P buttons
The local P buttons are the display cursor buttons of the 
EZ800/EZD basic unit. You can scan the buttons in both Run 
and Stop mode. 
Only one byte has to be transferred for the P buttons.
J
Ensure that the P buttons are also activated via the 
SYSTEM menu (in the basic unit).
Byte
Meaning
Value (hex), sent by
Master
Slave
0
Toggle byte
J
page 94
1
Command: Read
91
Response:
Read successful
C2
Command 
rejected
C0
2
Len
02
02
3
Type
06
06
4
Index
00
00
Data 1 (Low Byte)
00
J
Table 48
6 – 8
Data 2 – 4
00
00