EZ800/EZD Control Commands
MN05013001E
120
EZ800 
manual search term: MN05013004E. EZD manual search 
term: MN05013005E.
Read/write function block 
data
General notes
Always note the following when working with function blocks:
• The relevant data is transferred in Intel format. In other 
words, the first byte is the low byte (Byte 5) and the last byte 
(byte 8) the high byte. 
• The maximum data length is 4 bytes. All values must be 
transferred in hexadecimal format.
• All 32-bit values are treated as signed values. When 
transferring 32-bit values, ensure that the appropriate value 
range is suitable for long integers, i.e. signed.
32-bit value: –2147483648 .. 0 .. +2147483647
Please also note the relevant description of the function 
blocks provided in the EZ800 manual and the EZD manual.
The latest edition of these manuals are available as PDF 
files from the Internet at: