Eaton Electrical PROFIBUS-DP EZ204-DP ユーザーズマニュアル

ページ / 212
For more information visit: www.EatonElectrical.com
EZ800/EZD Control Commands
MN05013001E
154
7-day time switches HW01 .. HW32
Telegram structure
Table 89: Operand overview
Byte
Meaning
Value (hex), sent by
Master
Slave
0
Toggle byte
J
page 94
1
Command: Read
92
Response:
Read successful
C2
Command 
rejected
C0
2
Type
1C
1C
3
Instance
01 – 20
01 – 20
4
Index
J
Table 89
5 – 8
Data 1 – 4
00
depending on 
index, 
J
Table 90
Index 
(hex)
Operand
Read
Write
00
Bit IO 
J
Table 90
×
01
Mode/Parameter
02
Parameters 
J
Table 91
×
Channel A
03
Channel B
04
Channel C
05
Channel D