Eaton Electrical PROFIBUS-DP EZ204-DP ユーザーズマニュアル

ページ / 212
Read/write function block data
For more information visit: www.EatonElectrical.com
MN05013001E
175
Timing relays T01 .. T32
Telegram structure
Byte
Meaning
Value (hex), sent by
Master
Slave
0
Toggle byte
J
page 94
J
page 94
1
Command: 
Read
92
Write
B2
Response:
Read successful
C2
Write successful
C1
Command 
rejected
C0
2
Type
21
21
3
Instance
01 – 20
01 – 20
4
Index
J
Table 112
J
Table 112
5 – 8
Data 1 – 4
Read operation
00
depending on 
index, 
J
Table 113, 114
Write operation
depending on 
index, 
J
Table 113, 114