Installation
MN05013001E
20
Bus terminating resistors
The first and last station in a bus segment must be connected 
to the bus with the bus terminating resistor switched on. The 
bus terminating resistor is switched externally. This external 
switch function can either be implemented as a separate bus 
terminating resistor or with a special Sub-D plug with an 
integrated bus termination. 
Eaton's PROFIBUS-DP data plug enables both bus 
terminating resistors to be switched on and off.
EMC wiring
Electromagnetic interference may have adverse effects on the 
communication fieldbus. This can be minimized in advance by 
taking suitable EMC measures. These include:
• System design in accordance with EMC requirements, 
• EMC cabling and
• Measures that prevent the occurrence of large potential 
differences,
• Correct installation of the PROFIBUS system (cable, 
connection of bus connector,...).
The effects of electromagnetic interference can be 
significantly reduced by fitting the shield. The following two 
figures illustrate how to fit the shield.