Device Operation
MN05013001E
26
Setting the PROFIBUS-DP 
station address
Every PROFIBUS-DP station requires an unambiguous 
address in the PROFIBUS-DP structure. There are two ways 
of setting the PROFIBUS-DP addresses on the EZ204-DP:
• Using the integrated display and keypad on the EZ or EZD 
basic unit
• Using EZSoft on the PC.
Address range: 001 to 126
Setting the address on the basic unit with a display
Requirements:
• The basic unit (EZ700, EZ800 or EZD) and the EZ204-DP 
expansion unit must be fed with power.
• The basic unit has been unlocked (no password activated).
• The basic unit has a valid operating system version 
(J page 15).
• The basic unit must be in STOP mode.
• The EZ204-DP is not communicating with the PROFIBUS-
DP master (Bus LED is off).