PROFIBUS-DP Functions
MN05013001E
32
Diagnostics data
The EZ204-DP device features the standard diagnostics in 
accordance with the PROFIBUS specification.
Two additional diagnostics bytes are also sent.
GSD file
A PROFIBUS-DP GSD file is required for selecting the device 
and for running it on the PROFIBUS-DP communication bus. 
The GSD file contains standard PROFIBUS station 
descriptions. 
The file “EZ204DP.gsd” can be obtained at 
The file is also available on the 
EZSoft CD ROM.
Byte 0
Length of additional diagnostics bytes
Fixed 02
hex
00000010
Byte 1
Status of EZ-LINK
Value 00
hex
EZ-LINK is connected
Value 01
hex
EZ-LINK is disconnected