Eaton Electrical PROFIBUS-DP EZ204-DP ユーザーズマニュアル

ページ / 212
Read/write function block data
For more information visit: www.EatonElectrical.com
MN05013001E
79
Operating hours counters: O1 – O4
Telegram structure
Table 30: Operand overview
Byte
Meaning
Value (hex), sent by
Master
Slave
0
Toggle byte
J
page 44
1
Command: 
Read
89
Write
8D
Response:
Read successful
C2
Write successful
C1
Command rejected
C0
1
2
Type
92
92
3
Instance
2
00 – 03
00 – 03
4
Index
J
Table 30
5 – 8
Data 1 – 4
depending on index, J Table 31
1) Possible causes J page 91
2) EZ provides 4 operating hours counters O1 to O4. These can be 
addressed using the instance (0 – 3).
Index 
(hex)
Operand
Read
Write
00
Parameters J Table 31
×
01
Control byte J Table 32
×
02
Actual value
S1
2
×
c
1
03
Counter setpoint 2
S2
2
×
c
1
1) The value can only be written if it is assigned to a constant in the 
program.
2) A 32-bit value is transferred in data bytes Data 1 – Data 4. It should be 
remembered that the Data 1 is the low byte and Data 4 the high byte.