Parameter Description 
Action 
Setting/ 
Default 
P1000[1]** 
Selection of Frequency 
Setpoint 
(Speed Command Source) 
Selects the frequency setpoint 
source as follows: 
1 = Motor potentiometer 
setpoint/AOP 
2 = Analog input 
3 = Fixed frequency 
4 = USS on BOP  Link/AOP 
5 = USS on COM link 
6 = CB (Communications board 
or module) on COM link (P1/N2) 
1. Press   to advance to index 
[1], IN001, HAND. 
2. Press   to confirm index 
selection. 
3. Press   to advance to 1
4. Press   to confirm and save 
the setting. 
5. Press   again to return to the 
parameter selection level. 
Setting = 1 
Default = 1 
P1080 
Minimum Motor Frequency 
0 Hz to 650 Hz 
Minimum motor frequency at 
which the motor will run 
irrespective of the frequency 
setpoint. This value applies to 
both clockwise and 
counterclockwise rotation. 
1. Press   to advance to 
parameter P1080
2. Press   to access the 
parameter values level. 
3. Press   to advance to 
desired value. 
4. Press   to confirm and save 
the setting. 
Site Setting 
(20% to 30% 
Max) 
Default = 10 
** Parameters have two index settings: IN000 = Auto and IN001 = Hand.