Supported facility connections  24 
HP POD 240a security 
The HP POD 240a is equipped with standard key lock hardware at each personnel entry door and six 
external electrical cabinets. Each personnel entry door includes a door access contact that can be connected 
to the customer facility security system. Conduit and junction boxes are provided for customer installed 
controlled access systems. 
Additional options for controlled access security includes: 
 
Electronic card reader  
 
12-digit security code keypad 
 
Magnetic lock on each entry door 
 
Fire, safety, and security notifications 
Dry contacts are provided to enable the connection between the HP POD 240a fire alarm system and the 
customer facility fire system. If the HP POD 240a is connected to the customer facility systems, then the HP 
POD 240a-initiated alarms, notify the facility systems.  
The customer must provide an independent connection for each system listed in the following table. 
    
Alarm Meaning 
Fire prevention alarm  Smoke has been detected in the HP POD 240a. 
Fire suppression 
system (optional) 
The suppression system alarm has been activated, and 
gas will be dispersed to suppress a fire. 
Security 
A security breach has occurred. 
EPO 
The EPO system has been activated by an EPO button 
or thermal event, and shut down the HP POD 240a. 
 
The electrical layout of the fire alarm system is as described in the schematic drawing that is supplied with the 
HP Performance Optimized Datacenter (POD) 240a Operations and Maintenance Manual