White Rodgers 50A55-743 Drop-In Direct Replacement Furnace Control ユーザーズマニュアル

ページ / 8
2
SPECIFICATIONS 
INSTALLATION 
ELECTRICAL RATINGS [@ 77°F (25°C)]:
  Input Voltage: 25 VAC 50/60 Hz
 Max. Input Current @ 25 VAC: 0.45 amp
    Relay Load Ratings:
Valve Relay:  1.5 amp @ 25 VAC 50/60 Hz 0.6 pf
Ignitor Relay:  6.0 amp @ 120 VAC 50/60 Hz
 (resistive)
Inducer Relay:  2.2 FLA–3.5 LRA @ 120 VAC
Circulator Relay: 14.5 FLA–25.0 LRA @ 120 VAC
  Flame Current Requirements:
Minimum current to insure flame detection: 1 µa DC*
Maximum current for non-detection: 0.1 µa DC*
Maximum allowable leakage resistance: 100 M ohms
*Measured with a DC microammeter in the flame probe lead
OPERATING TEMPERATURE RANGE:
  -40° to 175°F (-40° to 80°C)
HUMIDITY RANGE:
  5% to 93% relative humidity (non-condensing)
MOUNTING:
  Surface mount multipoise
Timing Specs: (@ 60 Hz**)
 
maximum
Flame Establishing Time: 
0.8 sec
Flame Failure Response Time: 
2.0 sec
**At 50 Hz, all timing specifications should be increased 
by 20%
Gases Approved: Natural, Manufactured, Mixed, Liqui-
fied Petroleum, and LP Gas Air Mixtures are all approved 
for use.
50A55-743
Pre-Purge
15
Initial Ignitor Warm-up
(1
st
 64 attempts)
7
Minimum Ignitor Warm-up
5
Maximum Ignitor Warm-up
9
Ignition Activation Period
2
Trial for Ignition Period
4
Retries
2 times
Valve Sequence Period
12
Interpurge
30
Post-Purge
15
Lockout Time
300
Heat Delay-To-Fan-On
30
Heat Delay-To-Fan-Off*
90/120/150/180
Cool Delay-To-Fan-On
5
Cool Delay-To-Fan-Off
45
Auto Reset
60 minutes
Humidifier
Yes
Electronic Air Cleaner
Yes
*These times will vary depending on option switch 
position. See OPERATION section for further 
information
TIMING SPECIFICATIONS
(All times are in seconds, unless noted otherwise
MOUNTING AND WIRING
All wiring should be installed according to local and na-
tional electrical codes and ordinances.
The control must be secured to an area that will experience 
a minimum of vibration and remain below the maximum 
ambient temperature rating of 175°F. The control is ap-
proved for minimum ambient temperatures of -40°F.
Any orientation is acceptable.
Refer to the wiring diagram and wiring table when connect-
ing the 50A55 control to other components of the system.
UL approved, 105°C rated 18 gauge, stranded, 
2/64”
 thick 
insulation wire is recommended for all low voltage safety 
circuit connections. Refer to 50A55 specification sheet for 
recommended terminals to mate with those on the control.
UL approved 105°C rated 16 gauge min., stranded, 
4/64”
 
thick insulation wire is recommended for all line voltage 
connections. Refer to 50A55 specification sheet for rec-
ommended terminals to mate with those on the control.
After installation or replacement, follow appliance manu-
facturer’s recommended installation or service instructions 
to ensure proper operation.
The 50A55 has only one serviceable part–an automotive 
type fuse, which protects the low voltage transformer 
from damage if its output is short-circuited. If the fuse 
has opened up, remove whatever caused the short circuit 
and replace the fuse with only a 3 Amp automotive type 
fuse. If the fuse is not the cause of the control’s problem, 
replace the entire 50A55 control. There are no other user 
serviceable parts.
WARNING
!
FIRE HAZARD
•  Do not exceed the specified voltage.
•  Replace  existing  control  with  exact  model  and
dash number.
•  Protect the control from direct contact with water
(dripping, spraying, rain, etc.).
•  If the control has been in direct contact with water,
replace the control.
•  Label all wires before disconnection when servic-
ing controls. Wiring errors can cause improper and 
dangerous operation.
•  Route and secure wiring away from flame.
SHOCK HAZARD
•  Disconnect electric power before servicing.
•  Ensure proper earth grounding of appliance.
•  Ensure proper connection of line neutral and line
hot wires.
EXPLOSION HAZARD
•  Shut off main gas to appliance until installation is
complete.
CAUTION
!
Do not short out terminals on gas valve or primary
control. Short or incorrect wiring may damage 
the thermostat.