EXCEL 500/600 INSTALLATION INSTRUCTIONS 
REMOTE COMMUNICATIONS 
The following applies to the XC5010C and XCL5010, only. 
For remote communications with up to three XBS Building 
Centrals, a modem or ISDN terminal adapter can be 
connected directly to the serial port of the XC5010C CPU 
(either front or rear connection) or the serial port of the 
XCL5010. 
NOTE:  Remote communication via modem or ISDN terminal 
adapter requires firmware version V2.1.0 or higher. 
NOTE:  XBSi building supervisors are not supported for 
remote communication. 
Modem or ISDN Terminal Adapter
Connections 
The front serial port of the XC5010C CPU accepts a standard 
modem cable with a female 9-pin connector. 
Fig. 92. Serial port locations on Excel 500 
Use the cable that is supplied with the modem/ISDN terminal 
adapter. To connect to the terminals of the rear serial port of 
the XC5010C, use cable XW571 (length: 6 ft (1.9m)). 
Table 25. XW571 Connection 
Pin XC5010C 
RS232 signal 
Wire color 
2
 RTS
 
Blue
 
3
 GND
 
White
 
TxD 
Yellow 
RxD 
Green 
CTS 
Violet 
7
 DTR
 
Black
 
8 (not used) 
SG 
White 
DCD 
Brown 
10 
Shield 
Clear 
11 (not used) 
RI 
Red 
NOTE:  Pin numbers shown are for the rear connector of the 
XC5010C Computer Module. 
The serial port of the XCL5010 CPU accepts a standard 
modem cable with a female 9-pin connector. 
Fig. 93. Serial port location on Excel 500-XCL5010 
Use the cable that is supplied with the modem/ISDN terminal 
adapter. The communication speed is 9600 baud by default 
but can be set as high as 38.4 Kbaud. 
NOTE:   See section "Serial Port" on page 32, for signals of 
serial port. 
Modem Requirements 
•   Modem must support Hayes compatible command set (not 
V150 or V151 = Microsoft command set) 
•   Modem must support alpha-numeric return codes 
•   Modem must follow serial baud rate of the CPU 
•   Modem must support auto-bauding (baud rate fall-back) 
•   When carrier detect (connect) is reported, the carrier must 
be on simultaneously at both modems (on CPU side and 
on XBS side)   use same modem 
•   After a switch-ON of the DTR line by the CPU or XBS, the 
modem must accept a dial command after 3 seconds 
•   Modem must answer AT commands in less than 3 
seconds 
No Set-up for Standard Modem Behavior 
If no special modem behavior is required, there is no need to 
set up or initialize the modem/ISDN terminal adapter. The 
XC5010C/XCL5010 CPU will automatically detect the device 
(MMI or modem) attached to the serial port and set the 
appropriate communication speed. The controller will also 
automatically adapt to alphanumeric return codes used by the 
modem. This automatic detection and adjustment can take up 
to 5 seconds. 
NOTE:   It is highly recommended to use a state-of-the-art 
modem and leave it in its factory setting. 