Honeywell Excell 500/600 Controll System 500-XCL5010 ユーザーズマニュアル

ページ / 48
EXCEL 500/600 INSTALLATION INSTRUCTIONS 
Protection fuse 
1 A, fast blow 
Max. RF power 
2 W at 900 MHz 
Power supply connector 
6-pin modular 
CE conformity: 
• 89/336/EC (EMC guideline) 
• 73/23/EC (Low voltage guideline) 
• 91/263/EC (Telecommunications devices guideline) 
Standards: 
• EMC: ETS 300 342-1 
• Safety: EN 60950 
• GSM network: TBR 19, TBR 20 
Serial Cable 
For connecting the M20T to the Excel 500 controller, a 
standard RS232 cable (9-pin V24 sub-D sockets) is required. 
GSM Antenna Requirements 
All major suppliers of GSM antennas can supply GSM900 
Antennas with FME plugs to connect with the M20 Terminal 
for a variety of applications. Some antenna examples are 
shown below. 
The antenna must satisfy the following electrical 
requirements: 
Frequency TX 
890-915 MHz 
Frequency RX 
935-960 MHz 
Impedance 
50 ohms 
VSWR TX: 
max. 1.7:1 installed 
VSWR RX: 
max. 1.9:1 installed 
Gain 
> 1.5 dB referenced to 
λ/2 dipole 
3dB width of cone 
vertical: 
80° 
horizontal: 
360° 
Max. power: 
1 W (cw), 2 W peak; at ambient 
temperature of 55°C 
Depending on the application and the RF field at the local 
site, the GSM antenna may be mounted directly or via cable. 
The maximum antenna cable length is 8.0 m (including 20 cm 
M20 Terminal-cable) 
NOTE:   The maximum number of push/pull cycles shall not 
exceed 100. 
The antenna interface connector of the M20 unit is a FME 
connector (of type SMR nano (male)). Hence, the connector 
on the GSM antenna or antenna cable has to be of type SMR 
nano (female, or use a double female connector in between). 
Antenna Examples 
Fig. 95. Round radiation antenna, magnetic base, 5 DBi 
Fig. 96. Directional antenna (YAGI), 12 DBi 
Fig. 97. Round radiation antenna, 6.5 DBi 
Fig. 98. Window patch antenna, 2 DBi 
EN1R-1047GE51 RR0902  
46