Eaton Electrical Wireless Office Headset SC200 ユーザーズマニュアル

ページ / 78
DCTools Setup 
 
Copyright © 2005-2006 Eaton Corporation.  All Rights Reserved. 
IPN 997-00012-41D    December 2006 
6-3
 
DCTools Setup 
For your chosen communications option, configure the communications settings, in DCTools 
according to the table below. 
Then check that DCTools communicates correctly. 
 
Properties Direct 
Connection 
Ethernet  
Comms 
Enabled 
True True  
Protocol 
S3P S3P  
Connect Using 
COM1 
Local Network 
 
S3P Address 
0
 
0
 
 
Server IP Address 
– 
10.64.129.1  
(See Note 1)
   
Server Port 
– 
14000 
 
Telnet – 
Cleared 
 
Note 1:  Allocated by network administrator 
 
 
 
SM45 Ethernet Setup 
Before an SM45 supervisory module can communicate over an IP network with DCTools, the 
SM45 must be set up for Ethernet communications. 
Use the front panel or DCTools for configuring the SM45 supervisory module for Ethernet 
communications. 
Setup of Ethernet communications requires the following: 
• 
The network administrator assigning a unique IP address to each SM45 supervisory 
module to be connected to the IP network 
• 
Setting the assigned IP address for each SM45 
• 
Setting the net mask / subnet mask and gateway address for each SM45 as appropriate 
 
 
► 
To configure the SM45 for Ethernet communications using DCTools 
From the DCTools System Summary (Home) screen, click the Configuration hotlink and 
then Communications to display the Communications view. 
Under Ethernet, enter the assigned IP address, subnet mask and gateway address.