Johnson Controls M9220-GGX-3 ユーザーズマニュアル
M9220-GGx-3 Proportional Electric Spring Return Actuators Installation Instructions
11
Technical Specifications
M9220-GGx Proportional Electric Spring Return Actuators (Part 1 of 2)
Power Requirements
AC 24 V (AC 19.2 to 30 V) at 50/60 Hz: Class 2 (North America) or SELV
(Europe), 15.5 VA Running, 7.7 VA Holding Position;
DC 24 V (DC 21.6 to 24.4 V): Class 2 (North America) or SELV
(Europe), 6.7 W Running, 2.9 W Holding Position
(Europe), 15.5 VA Running, 7.7 VA Holding Position;
DC 24 V (DC 21.6 to 24.4 V): Class 2 (North America) or SELV
(Europe), 6.7 W Running, 2.9 W Holding Position
Transformer Sizing
Requirements
Requirements
20VA Minimum per Actuator
Input Signal/Adjustment
Factory Set at DC 0 to 10 V, CW Rotation with Signal Increase;
Selectable DC 0 (2) to 10 V or 0 (4) to 20 mA with Field Furnished
500 ohm, 0.25 W minimum resistor;
Switch Selectable Direct or Reverse Action with Signal Increase
Selectable DC 0 (2) to 10 V or 0 (4) to 20 mA with Field Furnished
500 ohm, 0.25 W minimum resistor;
Switch Selectable Direct or Reverse Action with Signal Increase
Control Input Impedance
Voltage Input: 200,000 ohms;
Current Input: 500 ohms with Field Furnished 500 ohm Resistor
Current Input: 500 ohms with Field Furnished 500 ohm Resistor
Feedback Signal
DC 0 (2) to 10 V for Desired Rotation Range up to 90°;
Corresponds to Rotation Limits, 1 mA Maximum
Corresponds to Rotation Limits, 1 mA Maximum
Auxiliary Switch Rating
GGC Models
Two Single-Pole, Double-Throw (SPDT), Double-Insulated Switches with
Gold Flash Contacts:
AC 24 V, 50 VA Pilot Duty;
AC 120 V, 5.8 A Resistive, 1/4 hp, 275 VA Pilot Duty;
AC 240 V, 5.0 A Resistive, 1/4 hp, 275 VA Pilot Duty
Gold Flash Contacts:
AC 24 V, 50 VA Pilot Duty;
AC 120 V, 5.8 A Resistive, 1/4 hp, 275 VA Pilot Duty;
AC 240 V, 5.0 A Resistive, 1/4 hp, 275 VA Pilot Duty
Spring Return
Direction is Selectable with Mounting Position of Actuator:
Side A, Actuator Face Away from Damper for CCW Spring Return;
Side B, Actuator Face Away from Damper for CW Spring Return
Side A, Actuator Face Away from Damper for CCW Spring Return;
Side B, Actuator Face Away from Damper for CW Spring Return
Running and Spring Return
Torque
Torque
177 lb·in (20 N·m) for a Single Actuator;
354 lb·in (40 N·m) for Two Like Models Mounted in Tandem
531 lb·in (60 N·m) for Three Like Models Mounted in Tandem
354 lb·in (40 N·m) for Two Like Models Mounted in Tandem
531 lb·in (60 N·m) for Three Like Models Mounted in Tandem
Rotation Range
Adjustable from 30 to 90° CW or CCW with Optional
M9220-603 Adjustable Stop Kit; Mechanically Limited to 90°
M9220-603 Adjustable Stop Kit; Mechanically Limited to 90°
Rotation Time
Power On
(Running)
(Running)
150 Seconds for 0 to 177 lb·in (0 to 20 N·m) at All Operating Conditions;
Independent of Load
Independent of Load
Power Off
(Spring
Returning)
(Spring
Returning)
11 to 15 Seconds for 0 to 177 lb·in (0 to 20 N·m) at Room Temperature;
35 Seconds Maximum for 0 to 177 lb·in (0 to 20 N·m) at -22°F (-30°C)
130 Seconds Maximum for 0 to 177 lb·in (0 to 20 N·m) at -40°F (-40°C)
35 Seconds Maximum for 0 to 177 lb·in (0 to 20 N·m) at -22°F (-30°C)
130 Seconds Maximum for 0 to 177 lb·in (0 to 20 N·m) at -40°F (-40°C)
Cycles
60,000 Full Stroke Cycles; 1,500,000 Repositions
Audible Noise Rating
Power On
(Running)
(Running)
<45 dBA at 39-13/32 in. (1 m)
Power On
(Holding)
(Holding)
<20 dBA at 39-13/32 in. (1 m)
Power Off
(Spring
Returning)
(Spring
Returning)
<55 dBA at 39-13/32 in. (1 m)
Electrical Connections
Actuator
(All Models)
(All Models)
48 in. (1.2 m) Halogen-Free Cable with 18 AWG (0.75 mm
2
) Wire Leads
Auxiliary
Switches
(GGC Models)
Switches
(GGC Models)
48 in. (1.2 m) Halogen-Free Cable with 18 AWG (0.75 mm
2
) Wire Leads
Conduit Connections
Integral Connectors for 3/8 in. (10 mm) Flexible Metal Conduit