Johnson Controls M9220-GGX-3 ユーザーズマニュアル

ページ / 12
M9220-GGx-3 Proportional Electric Spring Return Actuators Installation Instructions
6
6.
Rotate the damper blades to the desired position if 
the power is lost. To ensure a tight seal, insert the 
manual override crank and turn it in the direction 
indicated by the arrow on the label five turns; the 
position indicator should be near the 0° position on 
the scale. Quickly rotate the manual override crank 
a half turn in the opposite direction to temporarily 
lock the actuator hub in place.
7.
Evenly hand tighten each clamp nut onto the 
U-bolt, keeping the actuator flat. Secure the U-bolt 
to the damper shaft and tighten to a torque of 100 
to 125 lb·in (11 to 14 N·m).
8.
To release the spring, turn the manual override 
crank in the direction indicated on the label; the 
actuator spring returns to its starting position. If this 
step is omitted, the spring releases automatically 
when power is applied to the actuator.
9.
Remove the manual override crank and store it in 
an unused mounting hole.
10. Apply power long enough for the actuator to travel 
a full stroke, and verify that the actuator rotates 
freely throughout the range.
Note: If electric power is not available, complete 
this verification by reinserting the manual override 
crank and turning it in the direction indicated to 
rotate the coupler to the fully open position.
Rotation Range Using Optional 
M9220-603 Adjustable Stop Kit
The actuator is factory set for 90° rotation, and its 
rotation range is limited in 5° increments to a minimum 
of 30°. Stroke limiting stops are attached in the field to 
the shaft coupler side of the actuator to reduce the 
rotation range. Attaching a stroke limiting stop in the 
furthest mounting position reduces the rotation range of 
the actuator by 5°. Each progressive mounting position 
reduces the rotation range an additional 5°.
1.
Check that the damper blade is accessible or that 
its position is permanently marked on the end of 
the damper shaft as illustrated in Figure 7.
2.
Determine the desired rotation range. If a 65 to 
90° rotation range is desired, add one stroke 
limiting stop. If a 35 to 60° rotation range is desired, 
add two stroke limiting stops.
Note: If two stroke limiting stops are applied, use 
the manual override crank to position and lock the 
actuator in a mid-stroke position to gain access to 
both stroke limiting stop mounting positions.
3.
Mount the stroke limiting stops in the desired 
position using the two M4 x 10 mm self-tapping 
screws provided. Tighten the screws to a torque of 
35 lb·in (4 N·m).
4.
Manually reposition the coupler so that the coupler 
set screw aligns with the nodule guide that 
corresponds to the value determined in Step 2.
Example:
For a rotation range of 65°, mount one stroke 
limiting stop in the minimum stroke position as 
illustrated in Figure 8.
Figure 7: Damper Position Icons
FI
G
:d
am
pos
Figure 8: One Stroke Limiting Stop 
Mounted in the Minimum Stroke Position for a 
Rotation Range of 65°
A
90
-5
10
20
30
40
50
60
70
80
Sweep Angle
Indicated in 5
Increments
°
Shaft Position
Pointer 
Adjustment Holes
(Qty Two Groups
of Eight)
Lock Screw 
(Qty Two)
F
IG
:ra
nge
65
Stroke Limiting
Stop (Qty Two)