Meridian Data SecurStor iSCSI to SATA-II RAID Subsystem 16i ユーザーズマニュアル
SecurStor 16i Installation and Hardware Reference Manual
5-4
Figure 5-1: Loosening the Retention Screws from the BBU Module
Step 6.
Loosen the retention screws from controller. Use a medium-size
Phillips screwdriver to remove the screws underneath each of the
ejection levers. Keep the screws for future use.
Figure 5-2: Loosening the Retention Screws from the Controller Module
Step 7.
Disconnect all cables from the controller module. These include the
cables connecting to host or cascaded subsystems, and any cables
connecting the COM ports.
Step 8.
Remove the controller module by pressing down the two ejection
levers. The controller will automatically be eased out of the module
bay. Gently pull the controller module out of the subsystem with one
hand underneath to support the weight of the module.