Weil-McLain Gas Burner データシート

ページ / 4
Weil-McLain 88 Water and Steam Boilers — Series 2 — 
For Gas, Light Oil, & Gas/Light Oil-Fired Burners
2
Part No. 550-142-029/0508
Burner data
Table 1 
Boiler 
Model 
Number
Burner Input
Positive 
Pressure 
In Firebox
In. W.C.
Standard 
Burner Model Designation
Standard 
Combustion Control
Standard 
Control System
Burner Motor 
3450 Rpm
Standard 
Motor 
Voltage
No. 2 Oil 
Gph
Gas 
Mbh
Gas
Light
Oil
Gas/Light Oil
Gas
Light
Oil
Gas/Light 
Oil
Gas
Light
Oil
Gas/Light 
Oil
Gas
Light
Oil
Gas/
Light 
Oil
488R
6.9
996
0.80
WCR1-G-12
WCR1-OS
WCR1-GO-12
RM7897A
R7184P
RM7897C OO
FALFS
OO/FALFS
Z\x
Z\x
Z\x
120/60/1
488
7.0
1,010
0.80
WCR1-G-12
WCR1-OS
WCR1-GO-12
RM7897A
R7184P
RM7897C OO
FALFS
OO/FALFS
Z\x
Z\x
Z\x
120/60/1
588
9.4
1,356
0.58
WCR1-G-12
WCR1-OS
WCR1-GO-12
RM7897A
R7184P
RM7897C OO
FALFS
OO/FALFS
Z\x
Z\x
Z\x
120/60/1
688
11.8
1,701
0.46
WCR2-G-15
WCR2-OAS WCR2-GO-15
RM7897A
R7184P
RM7897C LHO
LHO
LHO/LHO
Z\x
C\v
C\v
120/60/1
788
14.2
2,046
0.47
WCR2-G-15
WCR2-OAS WCR2-GO-15
RM7897A
R7184P
RM7897C LHO
LHO
LHO/LHO
Z\x
C\v
C\v
120/60/1
888
16.6
2,382
0.49
WCR2-G-20A WCR2-OBS WCR2-GO-20A RM7897A
R7184P
RM7897C LHO
LHO
LHO/LHO
C\v
1
1
240/60/1
988R
17.2
2,482
0.50
WCR2-G-20B WCR2-OBS WCR2-GO-20B RM7897A
R7184P
RM7897C LHO
LHO
LHO/LHO
1
1
1
240/60/1
988
18.8
2,737
0.50
WCR2-G-20B WCR2-OBS WCR2-GO-20B RM7897C
R7184P
RM7897C LHO
LHO
LHO/LHO
1
1Z\x
1Z\x
240/60/1
1088R
20.0
2,887
0.52
WCR2-G-20B WCR2-OBS WCR2-GO-20B RM7897C RM7897A RM7897C LHO
LHO
LHO/LHO
1
1Z\x
1Z\x
240/60/1
1088
21.5
3,082
0.73
WCR3-G-20
WCR3-O
WCR3-GO-20
RM7897C RM7897A RM7897C LHO
LHO
LHO/LHO
1Z\x
2
2
240/60/1
1188
23.5
3,428
0.53
WCR3-G-20
WCR3-O
WCR3-GO-20
RM7897C RM7897A RM7897C LHO
LHO
LHO/LHO
1Z\x
2
2
3-Phase*
1288
26.0
3,773
0.48
WCR3-G-20
WCR3-O
WCR3-GO-20
RM7897C RM7897A RM7897C LHO
LHO
LHO/LHO
1Z\x
2
2
3-Phase*
1388
28.5
4,119
0.56
WCR3-G-25
WCR3-O
WCR3-GO-25
RM7897C RM7840L RM7840L LHO
LHO
LHO/LHO
1Z\x
2
2
3-Phase*
1488
31.0
4,464
0.58
WCR3-G-25B WCR3-OB
WCR3-GO-25B RM7840L RM7840L RM7840L LHO
LHO
LHO/LHO
3
3
3
3-Phase*
1588
33.0
4,809
0.59
WCR3-G-25B WCR3-OB
WCR3-GO-25B RM7840L RM7840L RM7840L LHO
LHO
LHO/LHO
3
3
3
3-Phase*
1688R
34.5
4,979
0.80
WCR3-G-25B WCR3-OB
WCR3-GO-25B RM7840L RM7840L RM7840L LHO
LHO
LHO/LHO
3
3
3
3-Phase*
1688
35.5
5,155
0.80
WCR3-G-25B WCR3-OB
WCR3-GO-25B RM7840L RM7840L RM7840L LHO
LHO
LHO/LHO
3
3
3
3-Phase*
1788
38.0
5,494
0.62
WCR4-G-25
WCR4-OA
WCR4-GO-25
RM7840L RM7840L RM7840L LHO
LHO
LHO/LHO
3
5
5
3-Phase*
1888
40.5
5,845
0.69
WCR4-G-25
WCR4-OA
WCR4-GO-25
RM7840L RM7840L RM7840L LHO
LHO
LHO/LHO
3
5
5
3-Phase*
* 208/60/3, 240/60/3, 480/60/3 burner motor voltage must be specified.
Burner specifications and settings
Burner capacities listed for elevations up to 2,000 feet.  For higher eleva-
1. 
tions, consult local Weil-McLain distributor/agent or sales office.
Light oil ratings based on No. 2 fuel oil with heating value of 140,000 
2. 
Btu per gallon.
Gas ratings based on natural gas with heating value of 1,000 Btu per 
3. 
cubic foot and specific gravity of 0.60.  Gas burners for other gases are 
available.  Consult local Weil-McLain distributor/agent or sales office.
Boiler-burner unit to be adjusted to achieve +0.10 inches W.C. pressure 
4. 
at the flue collar, resulting in positive pressure in firebox as listed.
Minimum gas pressures listed are subject to variations due to job condi-
5. 
tions.  Gas burners for other gas pressures are available.  Consult local 
Weil-McLain distributor/agent or sales office.
Tee pressures shown are for initial start-up.  Final pressure should be 
6. 
determined after checking actual gas flow and combustion readings.
120/60/1 control circuit is used for all burners.
7. 
Control circuit transformer is available as an option.
8. 
Motor relay or contactor will be furnished for all units, except 488R 
9. 
and 488.
Airflow safety switch is standard for all gas and combination gas/light 
10. 
oil units.
Burners will be completely assembled and wired (except gas train) and 
11. 
factory test-fired.
Burners listed by Underwriters Laboratories, Inc., state of Connecti-
12. 
cut, Fire Marshal state of Massachusetts, city of New York MEA, and 
others.
Special  controls  can  be  provided  to  meet  other  code  requirements 
13. 
not listed.  Consult your local Weil-McLain distributor/agent or sales 
office.
Electric gas pilot will be furnished as standard equipment on all gas and 
14. 
combination gas/light oil units.
Direct spark ignition is standard for light oil units.  Direct spark ignition 
15. 
is available as an option for combination gas/light oil units.  Consult 
your local Weil-McLain distributor/agent or sales office. 
Gas Control Systems:
16. 
OO
 
On-off operation, low fire start, high fire run.  Single-position 
air, adjustable opening gas valve.
LHO
 
On-off  operation,  low  fire  start,  high  fire  run.    488-1388: 
two-position air controlled by damper arm on motorized gas 
valve, fixed damper pre-purge.  1488-1888: two-position air 
controlled by separate motor, open damper pre-purge.
LHL
 
Low-high-low-off firing conditions.  488-1388: two-position 
air controlled by damper arm on motorized gas valve, fixed 
damper pre-purge.  1488-1888: two-position air controlled by 
separate motor, open damper pre-purge.
MOD
 
On-off operation, with proven low fire start and full modulating 
firing conditions with combustion air control. Proportional 
motor drives fuel metering valve and combustion air damper 
according to the firing conditions. Fixed damper pre-purge on 
488-1388, open damper pre-purge on 1488-1888.
Notes for Table 1 and Table 2