Honeywell Aquastat L8148A 取り扱いマニュアル

ページ / 8
L8148A,E,J AQUASTAT® RELAYS
95-6940—12
WARNING
Electrical Shock Hazard.
Can cause severe injury, death or property 
damage.
1. Disconnect power supply before beginning 
installation to prevent electrical shock or 
equipment damage.
2. Never apply a jumper across (or short) 
terminals B1, B2, or B3. This burns out the 
transformer.
Mounting
The L8148A,J has a case that can be converted to either 
horizontal or vertical mounting (Fig. 1).
Fig. 1. Case is designed for vertical
or horizontal mounting.
New Installation
Order well assemblies and 124904 Well Adapter  for the 
Aquastat Relay separately; refer to form 68-0040, Wells 
and Fittings for Temperature Controllers. Boilers usually 
have tappings that allow the well to be mounted 
horizontally so boiler water of average temperature can 
circulate freely.
1. Turn off all power and drain the boiler.
2. If no tapping is provided, prepare properly sized 
and threaded tapping near the top of the boiler.
3. Coat the well threads sparingly with pipe dope; 
install the well in the boiler tapping and tighten 
securely.
NOTE: Do not attempt to tighten by using the case as a 
handle.
4. Refill boiler and check for water leakage.
5. Insert the bulb element into the well until it bottoms. 
If necessary, slightly bend the tube inside the case 
to hold the bulb against the bottom of the well.
6. Center the loop of excess tubing in front of the 
immersion well so it cannot touch any electrical 
parts.
NOTE: Some models have an adjustable tubing length 
to 3 in. (76 mm). For these models, pull out 
extra tubing from inside the case, if needed.
7. Fit the case into the well so the clamp on the case 
slides over the flange on the well.
IMPORTANT
Best thermal response is obtained with a well 
that snugly fits the sensing bulb. Insert the bulb 
until it rests against the bottom of the well. Use 
a well of correct length and bend the tubing, if 
necessary, to hold the bulb against the bottom 
of the well, but do not make a sharp bend in the 
tubing.
If the well is not a snug fit on the bulb, use the 
heat-conductive compound (furnished with 
TRADELINE® models) as follows: Fold the 
plastic bag of compound lengthwise and twist it 
gently. Then snip off end of bag and work the 
open end of bag all the way into the well. Slowly 
pull the bag out while squeezing it firmly to 
distribute compound evenly in the well. Bend 
the tubing, if necessary, to hold the bulb against 
the bottom of the well and to hold outer end of 
the bulb in firm contact with the side of the well. 
See Fig. 2. Wipe excess compound from the 
outer end of the well.
Replacement Installation
Turn off all power and remove the old control. Refer to 
the cover insert of the old control to identify and tag each 
external lead as it is disconnected. If old well is 
unsuitable for new installation, remove it and proceed 
with instructions for new installation. If old well is suitable, 
use it and a 124904 immersion well adapter (ordered 
separately from form 68-0040, Wells and Fittings for 
Temperature Controllers) for the installation. (If the well 
clamp fits directly over the flange of the existing well 
spud, adapter use is not necessary.) The adapter has a 
flange at the wide end that fits into the well clamp and is 
slotted lengthwise to accommodate both the capillary 
tube and the short length of tube extending from the bulb.
1. Loosen but do not remove the well clamp screw on 
the side of the control case.
2. Pull out the capillary until the bulb bottoms in the 
well. Place adapter (if used) around the capillary 
tube so it fits into the slot. See Fig. 2. Center the 
loop of excess capillary tubing in front of the 
immersion well so it cannot touch any electrical 
parts.
NOTE: Some models have a tubing length adjustable to 
3 in. (76 mm). For these models, extra tubing 
inside the case can be pulled out, if needed.
3. Make sure the wide end of the adapter fits into the 
hole in the case. Position immersion well clamp 
snugly over the flange on the adapter and tighten 
the clamp screw.
4. Insert sensing bulb into well as shown in Fig. 2. 
(Distribute the heat-conductive compound in the 
tube prior to bulb insertion.)
5. Securely tighten setscrew (if present on old well) 
against adapter.
BRACKET POSITION FOR 
VERTICAL MOUNTING
BRACKET POSITION FOR 
HORIZONTAL MOUNTING
M8890