Honeywell Aquastat L8148A 取り扱いマニュアル

ページ / 8
L8148A,E,J AQUASTAT® RELAYS
95-6940—12
Fig. 7. Wiring L8148J for multizone control.
OPERATION AND SETTING
High Limit
The high limit switch shuts off the burner when the boiler 
temperature exceeds high-limit setting. Because heating 
systems differ, the correct temperature setting for one 
system might not be correct for another. Follow the boiler 
manufacturer recommendation for proper setting. To set, 
remove cover, and turn dial until the desired setting is 
directly below the pointer.
The dial stop is factory-set at the high end of the limit 
scale. To adjust, use a small screwdriver to hold the stop 
away from the dial face, and turn the dial until the desired 
setting is below the pointer. See Fig. 8. Release pressure 
on screwdriver, and make sure the stop rests flat against 
the dial face.
WARNING
Explosion Hazard.
Can cause severe injury, death or property 
damage.
This product is intended for use only in systems 
with a pressure relief valve.
Switching Relay
The switching relay is controlled by the room thermostat. 
On a call for heat, the relay coil is energized, completing 
the line voltage circulator circuit and also the burner 
circuit, if the boiler water temperature is below the high 
limit setting.
Auto-Manual Switch
The AUTO-MANUAL switch (only L8148J millivolt 
models) makes it possible to operate the burner (in a 
system with a millivoltage gas valve) during an electrical 
power failure. With switch at MANUAL, the burner 
operates continuously until either the high limit setting is 
reached or the switch is reset to AUTO. The circulator, 
requiring line voltage, is inoperative. When power is 
restored, the switch must be set to AUTO to resume 
automatic burner operation.
L1 
HOT
L2
1
END SWITCH
END SWITCH
END SWITCH
TV
TP
W
Z
T
B1
B2
B3
C1
C2
L1
L2
G
4
4
TH1
PP
TH2
PP
TR
TH
THTR
LOW VOLTAGE GAS
VALVE (eg, VR8300)
MILLIVOLTAGE
GAS VALVE
POWERPILE®
L1 
HOT
L2
1
CIRCULATOR
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
L8184J POWERS TWO V8043E OR F ZONE VALVES, OR ONLY ONE V8043 WHEN AMBIENT 
TEMPERATURE EXCEEDS 77
o
F (25
o
C).  USE AN ADDITIONAL TRANSFORMER(S) TO 
POWER ADDITIONAL VALVES.
LINK MUST BE USED WHEN USING 24 VOLT GAS VALVE HOOKUP (B1–B3).  REMOVE LINK
WHEN MILLIVOLTAGE GAS VALVE IS USED (B1–B2).
ADD JUMPER.
CONTROL CASE MUST BE CONNECTED TO EARTH GROUND.  USE GROUNDING SCREW 
PROVIDED.
B1 IS 1/4 IN. TAB TERMINAL.
1
2
3
4
5
6
6
5
2
3
24 VOLT
THERMOSTAT
24 VOLT
THERMOSTAT
24 VOLT
THERMOSTAT
ZONE 3
ZONE 2
ZONE 1
L8148J
V8043F
V8043F
V8043F
M2887A