SPECIFICATIONS
kW
Volts*
Phase
Amp Draw
Breaker or
Copper
C o n d u i t
L1
L2
L3
Fuse Size
Wire Size
Size 
36
208
1
173
173
-
225
4/0
1-1/2" (38 mm)
208
3
100
100
100
125
1
1-1/4" (32 mm)
240
1
150
150
-
200
3/0
1-1/2" (38 mm)
240
3
86.7
86.7
86.7
125
1
1-1/4" (32 mm)
380
3
54.7
54.7
54.7
70
4
1" (25 mm)
480
3
43.3
43.3
43.3
60
6
3/4" (19 mm)
600
3
34.7
34.7
34.7
50
8
1/2" (13 mm)
39
208
1
187.5
187.5
-
250
250 kcmil
2" (51 mm)
208
3
108
108
108
150
1/0
1-1/4" (32 mm)
240
1
163.5
163.5
-
225
4/0
2" (51 mm)
240
3
94
94
94
125
1
1-1/4" (32 mm)
380
3
59.3
59.3
59.3
90
3
1" (25 mm)
480
3
47
47
47
60
6
3/4" (19 mm)
600
3
37.6
37.6
37.6
50
8
1/2" (13 mm)
40
380
3
61.6
61.6
61.6
90
3
1" (25 mm)
40.5
208
3
112.5
112.5
112.5
150
1/0
1-1/4" (32 mm)
240
3
97.5
97.5
97.5
125
1
1-1/4" (32 mm)
480
3
48.8
48.8
48.8
70
4
1" (25 mm)
600
3
39
39
39
50
8
3/4" (19 mm)
45
208
3
125
125
125
175
2/0
1-1/2" (38 mm)
240
1
188
188
-
250
250 kcmil
2" (51 mm)
240
3
108
108
108
150
1/0
1-1/4" (32 mm)
380
3
68.6
68.6
68.6
90
3
1" (25 mm)
480
3
54
54
54
70
4
1" (25 mm)
600
3
43.4
43.4
43.4
60
6
3/4" (19 mm)
54
208
3
150
150
150
200
3/0
2" (51 mm)
240
3
130
130
130
175
2/0
1-1/2" (38 mm)
380
3
82.0
82.0
82.0
125
1
1-1/4" (32 mm)
480
3
65
65
65
90
3
1" (25 mm)
600
3
52
52
52
70
4
1" (25 mm)
57
208
3
158.4
158.4
158.4
225
4/0
2" (51 mm)
240
3
137.3
137.3
137.3
200
3/0
2" (51 mm)
380
3
86.7
86.7
86.7
125
1
1-1/4" (32 mm)
480
3
68.6
68.6
68.6
90
3
1" (25 mm)
600
3
54.9
54.9
54.9
70
4
1" (25 mm)
CIRCUIT BREAKER & FUSED DISCONNECT SWITCH SIZES - 36 to 57 kW
Wire size is based on THHN wire for branch circuit protection at .91 derate factor. Circuit breakers and fused
disconnects are to be mounted remote and wired by contractor. Sizes are based on the 2002 NEC table 
310-16. Conduit size based on conductors plus ground wire sizing per Table C1 from Appendix C.
Only 6, 7 & 9 kW models can be field converted to single or three phase (open delta on 3 phase). Larger
branch circuit required than for balanced 3 phase of equal kW. Balanced 3 phase available, consult factory.
NOTE: 250 kcmil maximum wire size for terminal block.