MOUNT WATER HEATER ON THE WALL 
 
Determine the proper height and location for the water heater to be installed.  Consider the venting 
system, as well as the water and gas connections.  Allow enough room for servicing the water heater and 
maintain the clearances from combustible materials.  The water heater is supported on the wall by means 
of a top and bottom slotted angle bracket.  For convenience, the center hole of the bracket is slotted so 
that a center screw may be first installed in the wall for hanging the water heater on the wall.  Two more 
screws are then added on the ends of the bracket to secure the water heater.  Wall anchors should be 
used for the bracket holes unless the bracket lines up with a stud.  As an alternative, a suitable piece of 
plywood may be cut to span the wall studs and the brackets fastened to the plywood.  Make sure the 
anchors are rated to support the 55 pound (25 kg) weight of the water heater. 
 
Table 3.
 Water Heater Clearances. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
*4 inches (102 mm) for enclosed area; 1 inch (26 mm) for unenclosed area 
 
 
 
 
 
 
 
 
to Combustibles 
to Non-Combustibles 
 
TG-150I-N(X) 
TG-180I-N(X) 
TG-199I-N(X) 
TG-237I-N(X) 
TG-237I-N(X)A
TG-150I-N(X) 
TG-180I-N(X) 
TG-199I-N(X) 
TG-237I-N(X)A 
TG-237I-N(X)A 
Top of 
Water 
Heater 
6 inches 
(152 mm) 
12 inches 
(305 mm) 
2 inches 
(51 mm) 
2 inches 
(51 mm) 
Back of 
Water 
Heater 
0 (zero) 
0 (zero) 
0 (zero) 
0 (zero) 
Front of 
Water 
Heater 
6 inches 
(152 mm) 
24 inches 
(610 mm) 
6 inches 
(152 mm) 
24 inches 
(610 mm) 
Sides of 
Water 
Heater 
2 inches 
(51 mm) 
2 inches (51 
mm) 
1/2 inch 
(13 mm) 
1/2 inch 
(13 mm) 
Floor/ 
Ground 
12 inches 
(305 mm) 
12 inches 
(305 mm) 
12 inches (305 
mm) 
2 inches 
(51 mm) 
Vent 
0 (zero) 
4 inches * 
0 (zero) 
0 (zero) 
 
WARNING
 
For all closet installations, follow the minimum clearances to combustibles whether the closet door is 
combustible or non-combustible. 
 
 
 
The recommended minimum clearance for servicing is 24 inches (608 mm) in front of the water 
heater. 
NOTICE