VARIABLE SPEED DRIVE SCREEN
OVERVIEW
 
This screen displays information per tain ing to a Vari able 
Speed Drive (VSD).
DISPLAY ONLY
Motor Run (LED)
Indicates whether the digital output from the controls is 
commanding the motor to RUN.
Motor Current % Full Load Amps
Displays the motor current as a per cent age of the Full 
Load Amps (FLA) value. 
Current Limit Setpoint
Displays the current limit value in use. This value could 
come from a 0-20mA, 4-20mA, 0-10VDC or 2-10VDC 
input in An a log Remote mode, PWM signal in Digital 
Remote mode, MicroGateway interface in ISN mode or 
a  lo cal ly  pro grammed  value.
Pulldown Demand Time Left
Displays the time remaining in the pro grammed pull-
down period if the value is non-zero.
Output Voltage
Displays the output voltage measured to the motor.
Output Frequency
Displays the present output frequency to the motor.
Output Current - Phase A, B, C 
Displays the phase current measured to the motor.
Input Power
Displays the total Kilowatts measured by the VSD or 
Harmonic Filter, if installed.
kW Hours
Displays the cumulative amount of kilowatts used over 
time as the VSD motor controller operates.
Pre-Rotation Vane Position
Displays the pre-rotation vane position as a value be-
 tween 0 and 100%.
Harmonic Filter Data (Harmonic Fil ter 
installed only)
Supply kVA 
Displays the supply kva measured by the Þ lter.
Total Power Factor
Displays the relationship between the Input Power and 
the Supply kVA.
Voltage Total Harmonic Distortion - L1, L2, L3
Displays the Total Harmonic Distortion (THD) for each 
of the voltage lines as calculated by the Þ lter.
00360VIP
FIG. 19
OptiView Control Center