York R123 ユーザーズマニュアル

ページ / 156
FORM 160.55-O1 (604)
53
YORK INTERNATIONAL
Pulldown Demand Limit 
Allows the user to specify the current limit val ue (as a 
percentage of FLA) to which the chiller will be limited 
during the speciÞ ed pulldown limit time. This value will 
override the Motor Current Limit value during this time 
period. This function is used to provide energy sav ings 
following chiller start-up.
Pulldown Demand Time 
Allows the user to set a period of time for which the 
pulldown demand limit will be in effect after the chiller 
starts. 
Stability Limit 
 
 
 
Adjusting this value modiÞ es the pre-rotation vane con-
 trol algorithm when used in conjunction with an ACC.
Surge Margin Adjust   
When the ACC maps a surge point, it will begin to 
ad just the chiller command frequency and vane con-
trols at a certain “margin” from the mapped point. This 
pro gram ma ble value allows the service technician to 
mod i fy the “margin” at which these adjustments will 
begin to take place.
Manual Surge Point 
 
This key will force the ACC to map a surge detection 
at the present operating con di tions. Mapping a point at 
these conditions will cause the ACC to make ad just -
ments to the command frequency in the future in order 
to pre vent the chiller from operating at the con di tions 
mapped. USE WITH CAUTION.
ACC Auto Map Print (Enabled / Disabled)
The chiller monitors the ACC communications and 
when a surge point is mapped, a short report of system 
pa ram e ters  is  printed.  When this function is active, all 
other printing capability is disabled
.
ACC Map Report 
 
 
The chiller requests the entire surge map from the ACC. 
As the map is received, the parameters for each point 
are printed.
Surge Map Clear 
 
 
This key instructs the ACC to clear all of the surge points 
presently mapped. This key will require con Þ r ma tion  of 
its selection by entry of a special pass word. USE WITH 
CAUTION.
NAVIGATION
Home
Access Level Re quired: VIEW
Causes an instant return to the Home Screen.
 
VSD
Access Level Required: VIEW
Returns to the VSD Screen.
2