York R123 ユーザーズマニュアル

ページ / 156
YORK INTERNATIONAL
86
FORM 160.55-O1 (604)
OVERVIEW
(Flash Memory Card version C.MLM.02.02.xxx 
and later)
The desired data collection start/stop triggers are set up 
on this screen. The trend data collection can be set to start 
or stop based upon the status of up to two selected Trig-
gers. The Triggers can consist of dig i tal events or analog 
parameters compared to thresh olds. The Trig gers can 
be used individually or in combination. The digital and 
analog parameters are selected from the Common Slots 
Screen (or Mas ter Slot Numbers List in this book). 
The parameter selected as the Primary Trigger is com-
 pared to a value selected as the Primary Test, using the 
Primary Operator as a comparator. If it is eval u at ed as 
true, then the data collection is started or stopped (after 
any selected Trigger delay) per the selected Trigger 
Action. 
  
A Secondary Trigger can be evaluated with the Pri ma ry 
Trigger to start/stop data collection. The Pri ma ry to Sec-
ondary Operator is used to deÞ ne the Trigger combina-
tions required to be true to start/stop data col lec tion.  The 
Secondary Trigger is setup and evaluated the same as 
the Primary Trigger. 
ADVANCED TREND SETUP SCREEN
FIG. 39
Entry Þ elds are as follows: 
If Primary Trigger                     
Is Primary Operator  
Primary Test     
 
  
Primary to Secondary Operator
 
  
Secondary Trigger
Is Secondary Operator Secondary Test
Then Trigger Action the Data Collection
With a delay of Trigger Delay  
 
After the desired Triggers are set, the START key on 
the TREND Screen must be manually pressed before 
the triggers will be evaluated. While waiting for the 
trig gers to start or stop data collection, a status message 
is displayed in the upper right corner of the TREND 
Screen describing the pending action.  
DISPLAY ONLY
None
00484VIP
OptiView Control Center