System Installation
2.5.2
System Power (Redundancy)
The IMACS-200 provides power redundancy for any of the powering options. The supplies 
are factory-installed, and the external connectors to receive the powering options selected will 
be pre-installed on the unit. Figure 2-4 on page 2-5 high-lites the location of the Power Supply 
feeds.The 120VAC and 220VAC power inputs are lightly shaded, and the -48VDC and 
125VDC options are darkly shaded.
2.5.3
AC Power Supply and DC Power Supply Fuses
The AC power supply and DC Power Supply fuses are already built in to the supplies. These 
fuses are not field serviceable. When unpacking the unit, an AC power cord will be in the box 
for each of the AC power supplies ordered. The AC inlet connector is located in the rear 
corners of the chassis. For a single supplied unit, the rear right-hand connector will be 
equipped. Refer to the system specifications section in this manual for input power 
requirements.
2.5.4
System Power and Ground Connections
After installing the system, make the power and ground connections to the chassis as 
described in this section. A frame ground connection is provided in the right-rear corner of the 
IMACS-200 rear panel.
2.5.5
Grounding requirements
Due to the UL regulatory requirements, a mounting stud is required for connection of the AC 
input earth ground lead to the product chassis. The ground lead must be connected to the 
chassis using a No. 6 screw, which is included. When grounding the system, use 14 gauge 
solid wire for a single connection to the provided earth ground screw. The mounting location 
is labeled with the IEC 417 No. 5019 symbol to identify this as the AC earth ground 
connection point. This mounting stud is located next to the IEC 320 AC input connector.
2.5.6
Chassis with Power Supplies 
Figure 2-4 on page 2-5 shows the different power connections on the chassis.
For DC powered systems, the lower right and lower left-hand connections provide for 
separate, redundant power feeds to the system's pre-installed DC power supplies if so 
equipped. These two sets of leads provide a connection for separate, redundant power feeds 
to the system in a load-sharing mode.