NORSEMAN™ 1500/2500 FuRNAcE
 
VGZ-018 / 051809.0
chiMNEY coNNEctioNs
DRAFT
chimneys perform two functions. 
1).  As a means of exhausting smoke and flue gases 
which are the result of fuel combustion. 
2). The chimney provides “draft” which allows oxygen 
to be continuously introduced into the appliance, 
so that proper combustion is possible. 
NOTE: The furnace does NOT create draft. Draft 
is a function of the chimney. A draft of 0.05 water column 
0.1 Pa) is required for proper drafting to prevent back-
puffing, smoke spillage, and to maximize performance. 
(Gauges to measure chimney draft are readily available 
at furnace shops and are economical to purchase or 
rent.) Do not exceed draft setting. Over firing and risk 
of fire can occur.
 As of  April 1, 1987 all coal stoves must be installed 
using a factory built chimney that meets the “Type HT” 
requirement  of  uL  103  (when  using  a  factory  built 
chimney).
ImPORTANT INSTALLATION POINTS
1.  Size the chimney flue to the furnace pipe. (6” outlet 
pipe = 6” chimney flue)
2.  Avoid  using  elbows  except  as  necessary.  
Elbows  reduce  draft,  no  more  than  two  elbows 
should be used in any chimney run.
3.  Make sure all horizontal runs of connector pipe have 
a minimum outward rise of 1/4” per horizontal foot. 
This allows any condensation or creosote buildup 
to run back into the firebox.
mANUFACTURED ChImNEY
R E F E R   TO   c H I M N E Y   A N D   c H I M N E Y  
cONNEcTOR  MAKER’S  INSTRucTIONS  FOR  
INSTALLATION AND uSE.
carefully  follow  chimney  manufacturer’s  
instructions. use only a listed chimney. If your chimney 
starts  at  the  ceiling  (figures  13  &  14)  you  will  need 
enough 6” round black connector pipe to reach the ceil-
ing. The top of the chimney must be at least three (3) 
feet above the roof and be at least two (2) feet higher 
than any point of the roof within ten (10) feet (figure 13).  
use only 6” diameter listed chimney uL 103 HT. chim-
ney made to this listing is High Temperature rated to 
2100 degrees Fahrenheit. use chimney from only one 
manufacturer. Never mix brands. carefully follow the 
chimney manufacturer’s stated requirements and clear-
ances. use the chimney manufacturer’s attic guards, 
roof  supports,  flashing  and  fire  stops  when  passing 
through a ceiling. use a listed thimble when passing 
through a combustible wall. Do not use makeshift com-
promises during installation. 
NEvER USE A SINgLE-
wALL CONNECTION PIPE AS A ChImNEY!
When using a pre-existing chimney, have it’s condi-
tion and installation inspected before using. Make sure 
that the chimney meets all of the uL rating requirements 
listed above. Be aware that not all manufactured chim-
ney is of the uL 103 HT type.
NOTE:  It  is  recommended  that  you  contact  a 
licensed heating and cooling contractor (consult 
your local yellow pages) for chimney installation.
Manufactured chimney with the proper required uL 
listing is available from most home centers, hardware 
stores, and HVAc supply stores.
If you have access to the internet, you may wish 
to  view  chimney  manufacturers’  information  on-line. 
See,  www.duravent.com,  www.selkirkinc.com,  or  
www.mtlfab.com. 
Fig. 11 - Masonry Chimney Connection
mASONRY ChImNEY
Before  using  an  existing  masonry  chimney, 
clean  the  chimney,  inspect  the  flue  liner  and  make 
any repairs needed to be sure it is safe to use. Make 
repairs  before  attaching  the  furnace. The  connec-
tor  furnace  pipe  and  fittings  you  will  need  to  con-
nect  directly  to  a  masonry  chimney  are  shown  in  
figure 11 and 12. 
If the connector furnace pipe must go through a 
combustible wall before entering the masonry chimney, 
consult a qualified mason or chimney dealer. The instal-
lation must conform to local building and fire codes and 
latest edition of NFPA 211.
D O   N OT   C O N N E C T   T h I S   F U R N AC E 
INTO  ThE  SAmE  ChImNEY  FLUE  AS  ThE 
FIREPLACE,  gAS  APPLIANCE,  OR  A  FLUE  
CONNECTED wITh  ANY  OThER  APPLIANCE.
  
continued on next page