Utica Boilers UB90-100 インストール手順

ページ / 72
27
Figure 18   - Combustion Air and Vent Piping - Boiler Connections
COMBUSTION AIR AND VENT PIPE
2” (50.8mm) Diameter Vent And Combustion 
Air Intake Piping 
- 21 ft (6.4m)maximum total equivalent length 
for 90-100 models
-26 ft (7.9m) maximum total equivalent length 
for 90-50 and -90-75 models
- 2 ft (0.6m) minimum total equivalent length 
for all models
TRANSITION FITTING 
2” (50.8mm) 
⊘ to 3” (76.2mm) 
⊘ IN VERTICAL RUN
3” (76.2mm) Diameter Vent And Combustion 
Air Intake Piping
- 92 ft (28m) maximum total equivalent length 
for 90-100 models
- 15 ft (4.6m) minimum total equivalent length 
for 90-100 models
- 112 ft (34m) maximum total equivalent 
length for 90-50 and 90-75 models
- 20 ft. (6m) minimum total equivalent length 
for 90-50 and 90-75 models
SAFETY RELIEF 
VALVE SEE 
PAGE 18 FOR 
REQUIREMENTS
3”
SAFETY RELIEF 
VALVE SEE 
PAGE 18 FOR 
REQUIREMENTS