Utica Boilers UB90-100 インストール手順

ページ / 64
46
NEGATIVE PRESSURE SWITCH CHECK
BOILER 
STATUS
NEGATIVE
 PRESSURE (W.C.)
PRESSURE 
SWITCH 
CONNECTS
Not Running
0”
Normally 
Closed
Setpoint
-0.50” 
for Models 100 & 075
Running 
Without 
Blockage
Less Negative than 
Setpoint
Closed
Running 
With 
Blockage
More Negative than 
Setpoint
Open
To Gas Valve Vent
Gas Valve Vent
For use on Model - 100  boilers only.
• Following steps and diagram indicate locations of 
connection points required to check negative pressure.
• Negative pressure switch is safety device which 
prevents boiler from fi ring if there is air intake 
blockage.
• Turn off service switch, or lower thermostat setting.
• Remove vinyl cap from 4-way connector.
• Install test line as shown to inclined manometer or 
differential pressure gauge with ability to read 0.01” to 
5.0” w.c.
• Turn on service switch and set thermostat to call for 
heat.
• If manometer readings do not correspond to chart, 
check for possible causes:
A.  Blockage in air intake
B.  Undersized air intake 
C.  Loose blower wheel or motor shaft
D.  Incorrect pressure switch or pressure switch 
setpoint
• When pressure reading is correct and the pressure 
switch is operating properly, remove test line and 
reinstall vinyl cap to 4-way connector.
Negative Pressure Switch
Differential Air Pressure Switch
Red Transparent Vinyl Tubing
Tee 
Vinyl Cap
All pressure switch tubing 
is clear vinyl tubing unless 
otherwise noted.
Inclined Manometer                    
(Differential Pressure Gauge)
Test Line
To Air Inlet 
Sution Port
To Sight Glass Suction Port
White Silicone Tubing
4-Way  Connector
Models 075 and 100