Siemens Network Hardware D410 ユーザーズマニュアル

ページ / 150
 
Commissioning (software) 
 
4.12 Deleting data 
D410 
Commissioning Manual, 08/2008 Edition 
115
 
4.12.2 
Resetting the memory of SIMOTION D410 
Introduction 
A memory reset deletes all data from RAM on the SIMOTION D410 and non-volatile data in 
SRAM with the exception of the communication configuration (baud rates, network 
addresses, etc.). Data on the CompactFlash Card is retained if you reset the memory.  
Reset the memory on SIMOTION D410 if 
●  You want to undo changes made to user data (programs, configuration data, parameter 
assignments) which you have not backed up by means of the "Copy RAM to ROM" 
command. 
●  The RUN/STOP LED is flashing (slow flashing) to indicate that SIMOTION D410 is 
requesting a memory reset. 
●  Non-volatile data does not match the project on the CF card and an error is generated 
(diagnostics buffer entry). 
You can reset memory either in offline mode using the DIL switch of SIMOTION D410, or in 
online mode using SIMOTION SCOUT. 
Data deleted by memory reset 
The following data is deleted during a memory reset: 
●  User data (units, configuration data, parameters, task configuration) 
●  Technology packages 
●  Retain TO (absolute encoder adjustment) 
●  Retain variables 
Retain variables in the interface or implementation section of a UNIT are declared with 
VAR_GLOBAL RETAIN 
 
 
 
Note 
As a memory reset deletes all absolute encoder data the encoder must be re-adjusted 
after memory reset.