ページ / 150
 
Commissioning (software) 
 
4.2 Configuring the system in offline mode 
D410 
Commissioning Manual, 08/2008 Edition 
71
 
 
Figure 4-11  Configuration after HW Config alignment 
 
 
 
 
Note 
Repeat the HW Config alignment if the message frames for SINAMICS Integrated were 
changed. The addresses are not updated automatically. 
  
4.2.5 
Downloading the project to SIMOTION D410 
Procedure for downloading a project into the target system 
1.  Save and compile the project. 
2.  Go online to SIMOTION D410. 
3.  Select the "Download project to target system" command to download the project to 
SIMOTION D410. The connection to SINAMICS Integrated is activated automatically.  
The drive has been assigned parameters and commissioned. You can now test the drive 
using the drive control panel. 
 
 
Note 
Online access to SINAMICS Integrated is not possible if HW Config is not loaded at the time 
you initially connect to the target system. 
Download the data to HW Config in order to enable online access to SINAMICS Integrated.