Siemens Sitrans F FX300 ユーザーズマニュアル

ページ / 80
 TECHNICAL DATA 
8
69
SITRANS FX300
www.siemens.com/flow
06/2009 - SFIDK.PS.050.F2.02   A5E02100423
Process connections
Flange version
Flange version
Flange version
Flange version
DIN EN 1092-1
DN15...300 in PN16…100
ASME B16.5
½...12" in 150…600 lbs
JIS B 2220
DN15...300 in JIS 10…20 K
For detailed information on combination flange/pressure rating, 
refer to chapter "Dimensions and weights".
Sandwich version
Sandwich version
Sandwich version
Sandwich version
DIN
DN15...100 in PN100 (higher pressures on request)
ASME
½...4" in 600 lbs (higher pressures on request)
JIS
DN15...100 in 10…20 K (higher pressures on request)
Electrical connections
Power supply
Non-Ex: 14…36 VDC
Ex: 14…30 VDC
Current output
Current output
Current output
Current output
Description of the used 
abbreviations
U
ext
 = external voltage; R
L
 = load + resistance
Measuring range
4...20 mA (max. 20.8 mA) + HART
®
 protocol
Load
Minimum 0 Ω; maximum RL = ((Uext. - 14 VDC) / 22 mA) 
Error signal
Acc. to NAMUR NE43
Upper value: ≥ 21.0 mA
Lower value: ≤ 3.6 mA (not with HART
®
 protocol)
Pulse output
Pulse output
Pulse output
Pulse output
Pulse rate
Max. 0.5 pulse/s (corresponds to 1800 pulses/hour)
Power supply
Non-Ex: 24 VDC as NAMUR or open < 1 mA, maximum 36 V, closed 
100 mA, U < 2 V
Ex: 24 VDC as NAMUR or open < 1 mA, maximum 30 V, closed 100 mA, 
U < 2 V
HART
HART
HART
HART
®
HART
®
 protocol via current output
Device revision
1
Physical layer
FSK
Device category
Transmitter, galvanically isolated
System requirements
Load min. 250 Ω
Multidrop operation
4 mA
Approvals and certifications
ATEX
ATEX II 2G EEx d ia [ia] IIC T6
FM
Class I, II, III
Div 1/2, groups A-G