DC 5000   Low Voltage Protection Relay 
 
The DC 5000 uses a Macromatic relay to monitor the voltage at the compressor motor.  
The relay has an adjustable pick up voltage (reset).  A red indicator lamp lights when 
the relay is on. This lamp turns green when the relay senses low voltage and turns off. 
 
This relay is designed to protect the compressor motor from low voltage damage as well 
as protecting the batteries from deep discharge. 
 
How It Works 
 
As an example, if the pick up voltage is set at 12.2 volts and the drop out voltage is set 
for 90 percent when the voltage drops 1.2 volts (10 percent of 12.2), the relay will turn 
off the compressor.  This would be at about 11 volts. The drop out voltage setting is 
dependant upon the pickup voltage setting. The compressor will remain off until the 
pickup voltage is restored to or above 12.2 volts by recharging the batteries. 
 
About Battery Voltage 
 
Battery voltage will drop as batteries are discharged.  Resistance in the wiring and wire 
size creates a lower voltage at the consumer than at the batteries.  Battery voltage will 
rise when the consumers are turned off.  As a result of this spring back to at rest voltage 
levels the voltage relay must be set for your particular installation. 
 
Setting The Control 
 
The control is mounted on the DC 5000 Electrical junction box.  The relay has a two 
knobs and an indicator lamp. 
  
Initial stetting: Set the pick up point at about 3 o’clock this should be about 12 volts.  Set 
the drop out voltage at the 3 o’clock position as a starter.  This should be about 90 
percent of 12 volts or 10.8 volts.  Use the 20-hour discharge rating of your battery bank 
and calculate 30% as a safe discharge level in amp/hours.  When properly set the 
compressor drawing 40 amps per hour should be able to safely use this battery amount 
without the protection relay switching off.  
 
Target: Set dropout voltage as high as possible (toward 95 percent) without dropping 
out when you know you have plenty of battery amp hours to go. Set pickup voltage at 
greater than 12 volts. 
Mark and log setting positions. 
 