Applied operation with input and output signals (operation by terminal board) 
7.2.1  Functions  of  input  terminals  (in  case  of  sink  logic)
Use the above parameters to send signals from an external programmable controller to various control input 
terminals to operate and/or set the inverter. 
The desired contact input terminal functions can be selected from 120 types. This gives system design flexibility. 
[Control terminal board]   
! !
■ Setting of contact input terminal function 
Terminal 
symbol 
Title 
Function 
Adjustment 
range 
Default setting 
H [Note 5], 
H, H
Always ON function selection 1~3 
~
Ÿ
 Refer to 
Section 
7.2.1. 
(No function is 
assigned) 
H
Input terminal function selection 1 (F) 
(Forward run) 
H
Input terminal function selection 2 (R) 
(Reverse run) 
ST 
H [Note 6], H Input terminal function selection 3 (ST) 
(Standby) 
RES 
H
Input terminal function selection 4 (RES) 
 (Reset) 
S1 
H
Input terminal function selection 5 (S1) 
 (Preset speed 1)
S2 
H
Input terminal function selection 6 (S2) 
(Preset speed 2)
S3 
H
Input terminal function selection 7 (S3) 
(Preset speed 3)
RR/S4 
H
Input terminal function selection 8 (RR/S4)
(Preset speed 4)
LI1~LI8 
H~H
Input terminal function selection 9~16 

B12~B15
H~H 
Input terminal function selection 17~20 

Note 1:RR/S4 terminal become enable when SW3 is switch to S4. 
Note 2: When H, H and H (Always ON function selection 1~3) are selected, selected function is 
generally activated regardless of positive or negative logic. 
Note 3: H~H is for use of expansion terminal board option unit. 
Note 4: H~H is not supported (for options). 
Note 5: VFAS1-****-WN, HN    Note 6: VFAS1-****-WP 
■ Connection method (An example of the connection of terminals: SW1 set to sink logic) 
1) In case of positive logic (a-contact) input 
Inverter 
A-contact switch
CC 
Input terminal 
!
This function is activated when the input 
terminal and CC (common) are short-circuited. 
Use this function to specify forward/reverse run 
or a preset speed operation. 
   
2) In case of negative logic (b-contact) input 

B-contact switch 
CC
Input terminal
!
This function is activated when the input 
terminal and CC (common) are open-circuit. 
Use this function to specify operation 
standby signal or reset signal. 
Inverter