Toshiba VF-AS1 ユーザーズマニュアル

ページ / 326
!
  E6581301!
H-3 
(Continued) 
Commun
ication 
No. 
Item displayed 
Key 
operated
LED 
display 
Description 
FE08 
CPU1 version 
X The version of the CPU1 is displayed. 
FE73 
CPU2 version 
Y The version of the CPU2 is displayed. 
FE10 
Past trip 1 
E
⇔
Past trip 1 (displayed alternately at 0.5-sec. intervals) 
FE11 
Past trip 2 
J! ⇔
Past trip 2 (displayed alternately at 0.5-sec. intervals) 
FE12 
Past trip 3 
R
⇔
Past trip 3 (displayed alternately at 0.5-sec. intervals) 
FE13 
Past trip 4 
PGTT
⇔ Past trip 4 (displayed alternately at 0.5-sec. intervals) 
FE79 
Part replacement 
alarm information 
O___
The ON/OFF status of each of the cooling fan, circuit 
board capacitor, main circuit capacitor or part 
replacement alarm of cumulative operation time is 
displayed in bits. 
ON:
OFF:_
FE14 
Cumulative 
operation time 
V    
The cumulative operation time is displayed. 
(Indication of 0.1 represents 10 hours.) 
Default display 
mode 
[Note 1]

The operation frequency is displayed (during operation).
Note 1: Press the 
  keys to change items displayed in the status monitor mode. 
Note 2: Contents of status indications of *1, *2, *3, *4, *5, *6, *7, *8, and *9 can be selected from 44 kinds of 
information. 
Contents of status indications that are set up at H (standard monitor display selection) and 
H~H (status monitor 1 to 8 display selection) are displayed. 
Unit of current and voltage indications can be changed from % to A (ampere)/V (volt) and vice versa 
respectively. Ÿ Refer to Section 5.15. 
Note 3: Indicated input voltage is DC voltage just after input voltage is rectified multiplied by 1
   2 . 
Note 4: The number of bars displayed varies depending on the setting of H (logic output/pulse train output 
selection.) 
The bar representing the OUT1 terminal is displayed only when logic output function is assigned to it.
If H=: The bar representing OUT1 is displayed. 
If H=: The bar representing OUT1 is not displayed. 
Note 5: Past rip records are displayed in the following sequence: 1 (latest trip record) 
⇔2⇔3⇔4 (oldest trip record). 
If there is no trip record, PGTT is displayed. 
Details on past trip record 1, 2, 3 or 4 can be displayed by pressing the  ENT   key when past trip 1, 2, 3 or 
4 is displayed. Ÿ For more details, refer to Section 8.2.2. 
Note 6: The part replacement alarm is displayed based on the value calculated from the annual average ambient 
temperature, operation time and load current specified using H. 
Use this alarm as a guide only, since it is based on a rough estimation. 
Note 7: The cumulative operation time increments only when the machine is in operation. 
MODE
O___K
Cooling fan
Cumulative 
operation time
Control circuit board 
capacitor  
Main circuit capacitor 
[Note 6]
[Note 7]
  [Note 5]
  [Note 5]
  [Note 5]
  [Note 5]