Toshiba VF-AS1 ユーザーズマニュアル

ページ / 326
!
  E6581301 
H-12 
8
(Continued) 
Commun
ication 
No. 
Item displayed 
Key 
operated
LED 
display 
Description 
FE10 
Past trip 1 
E
⇔ Past trip 1 (displayed alternately at 0.5-sec. intervals)
FE11 
Past trip 2 
J! ⇔ Past trip 2 (displayed alternately at 0.5-sec. intervals)
FE12 
Past trip 3 
R
⇔ Past trip 3 (displayed alternately at 0.5-sec. intervals)
FE13 
Past trip 4 
PGTT
⇔ Past trip 4 (displayed alternately at 0.5-sec. intervals)
FE79 
Part replacement 
alarm information 
O___K
The ON/OFF status of each of the cooling fan, circuit 
board capacitor, main circuit capacitor or part 
replacement alarm of cumulative operation time is 
displayed in bits. 
ON: 
OFF: _
FE14 
Cumulative operation 
time 
V
The cumulative operation time is displayed. 
(Indication of 0.1 represents 10 hours.) 
Default display mode 
! ! ! !
! ! ×2 
R! 
Status monitor mode (The code blinks if a trip occurs.)
Reverts to the first trip indication. 
Note 1: If trouble occurs while the CPU is being initialized after the inverter is turned on or reset, the trip record 
retaining function does not record it but displays a status monitor item. 
Note 2: Contents of status indications of *1, *2, *3, *4, *5, *6, *7, and *8 can be selected from 44 kinds of information. 
Contents of status indications that are set up at H~H (status monitor 1 to 8 display mode) are 
displayed. 
Note 3: Items displayed when a trip occurs can be changed by pressing              or                key. 
Note 4: You can switch between % and A (ampere)/V (volt), using the parameter FURW (current/voltage unit 
selection). 
Note 5: The input voltage displayed is 1/
   2   times as large as the rectified DC input voltage. 
Note 6: The number of bars displayed varies depending on the setting of H (logic output/pulse train output 
selection). The bar representing the OUT-NO terminal is displayed only when logic output function is assigned 
to it. 
If H=:The bar representing OUT-NO is displayed. 
If H=:The bar representing OUT-NO is not displayed. 
Note 7: Past rip records are displayed in the following sequence: 1 (latest trip record) 
⇔2⇔3⇔4 (oldest trip record). 
 
If there is no trip record, PGTT is displayed. 
Details on past trip record 1, 2, 3 or 4 can be displayed by pressing the              key when past trip 1, 2, 3 or 4 
is displayed. Ÿ For more details, refer to Section 8.2.2. 
Note 8: The time elapsed before an end of part replacement alarm is issued is calculated from the average yearly 
ambient temperature, operation time and load current entered using H, and it is no more than an 
estimation, and therefore it should be used for reference purposes only. 
Note 9: The cumulative operation time increments only when the machine is in operation. 
Note 10: At the occurrence of a trip, maximum values are not always recorded and displayed for reasons of detecting 
time. 
ENT
[Note  7]
[Note  7]
[Note  7] 
O___K
Cooling fan
Cumulative 
operation time
Control circuit board 
capacitor 
Main circuit capacitor 
MODE
[Note  9] 
[Note  7]
[Note  8]