9.1.2  Measures  to  satisfy  the  EMC  directive!!!!
Concrete measures for EMC directive of CE markings are shown below. 
 Models with a built-in EMC filter 
(1) 200V class: VFAS1-2004PL~2075PL 
400V class: VFAS1-4007PL~4500KPC 
The above mentioned models install EMC noise filter inside. So the conducted and radiated noise can be reduced, 
optional EMC noise filters are not needed. 
(If a further noise reduction is required, insert an additional filter described in I-4 on the input side of the inverter.) 
Table 2      EMC directive compliance 
Inverter type 
EMC plate type
Requirements 
Conducted noise 
IEC61800-3 category C2
(EN55011 classA Group1)
Conducted noise 
IEC61800-3 category C3
(EN55011 classA Group2)
PWM carrier 
frequencyEH
(kHz) 
Length of 
motor 
connecting 
cable 
(m) 
VFAS1-2004PL~
VFAS1-2015PL 
EMP101Z 
10 
Built-in filter 
16 
VFAS1-2022PL 
EMP102Z 
10 
16 
VFAS1-2037PL 
10 
Built-in filter 
16 
VFAS1-2055PL, 
VFAS1-2075PL 
EMP103Z 
10 
16 
VFAS1-4007PL~
VFAS1-4022PL 
EMP101Z 
10 
Built-in filter 
16 
VFAS1-4037PL 
EMP102Z 
10 
16 
VFAS1-4055PL~
VFAS1-4110PL 
EMP103Z 
10 
Built-in filter 
16 
VFAS1-4150PL 
EMP104Z 
10 
16 
VFAS1-4185PL 
2.5 
25 
16 
25 
VFAS1-4220PL 
EMP105Z 
2.5 
50 
16 
25 
VFAS1-4300PL, 
VFAS1-4370PL 
EMP106Z 
2.5 
50 
25 
VFAS1-4450PL~
VFAS1-4750PL 
EMP108Z 
2.5 
50 
16 
25 
VFAS1-4900PC 
2.5 
50 
VFAS1-4110KPC
2.5 
50 
VFAS1-4132KPC
2.5 
50 
VFAS1-4160KPC
2.5 
50 
VFAS1-4200KPC
2.5 
50 
VFAS1-4220KPC
2.5 
50 
VFAS1-4280KPC
2.5 
50 
VFAS1-4355KPC,
VFAS1-4400KPC,
2.5 
50 
VFAS1-4500KPC,
2.5 
50 
(    ): An optional regenerative braking unit PB7 is used.