Toshiba VF-AS1 ユーザーズマニュアル

ページ / 326
E6581301 
B-16 
2
2.3.3  RS485  communication  connector
The VF-AS1 is equipped with two connectors: a two-wire RS485 connector (on the operation panel) and a four-wire 
RS485 connector. The two wire RS485 connector is used to connect an external option (such as remote keypad or 
computer) to the inverter. To connect to a network, use the four-wire RS485 connector, following the instructions 
below.   
2-wire RS485 
4-wire RS485 
Signal 
name 
Pin 
number
Description 
Signal 
name 
Pin 
number
Description 
DA 
Same phase data 
RXA
Same phase reception data (positive line)   
DB 
Anti-phase data 
RXB
Anti-phase reception data (positive line) 
SG 
Ground line of signal data
TXA
Same phase transmitting data (positive line)
This table shows signal line of inverter side. 
TXB
Anti-phase transmitting data (positive line) 
* Never use pin-1, 2, 3, 6 and 7. 
SG 
2, 8 
Ground line of signal data 
This table shows signal line of inverter side. 
(Example: RXA signal is received by inverter.) 
* Never use pin-1 (P24) and pin-7 (P11). 
■ CRQQHFWLRQ diagram for 4-wire RS485 communication 
!
Terminating 
resistance!
100Ω    -1/4W!
AS1 (slave)!
Upper 
computer 
or 
VF-AS1 
(master)!
RXA!
!
RXB!
TXA!
TXB!
SG!
RXA!
RXB!
TXA!
TXB!
SG!
RXA!
RXB!
TXA!
TXB!
SG!
RXA!
RXB!
TXA!
TXB!
SG!
cross each other  !
straight!
straight!
AS1 (slave)!
AS1 (slave)!
■ Note 
* Separate the communication line and the main circuit wiring by 20cm or more.   
* Never use pin-1 (P24) and pin-7 (P11).   
* Connect RXA and RXB, between TXA and TXB using twisted pair cable.   
* Connect terminating resistances at both ends of a transmission line.   
* When using 2-wire type, short RXB to TXB and RXA to TXA.   
When connecting a communications device via the two-wire connector, carefully read the precautions for use in the 
operating manual for the communications device.   
* When connecting the VF-AS1 to other inverters, you do not need to connect the master receive lines (pins 4 and 5) 
or the slave send lines (pins 3 and 6).   
2-wire RS485 communication 
4-wire RS485 communication 
Pin-1
Pin-8